CoreLink
TM
P/N 3128012_A
21
CoreLink
™
Case Controller
U.S. & Canada 1-800-922-1919 • Mexico 1-800-890-2900 • WWW.HUSSMANN.COM
5.3
System Data : C0: More , System Data
To change Temperature, Pressure and Light units, Refrigerant & Case Type, use this tab
Navigate to C0: More and then to System Data to check 5 Read/Write description of
temp, pressure & Refrigerant and case type as below. Check for correct data. If not
press F3 to edit parameter list
E2 Parameter
Description
Range
TEMP_UNITS
Temperature units
0, "Celsius", 1,
"Fahrenheit"
PRESS_UNITS
Pressure units
0, "PSI", 1, "BAR"
REFRIG_TYPE
GAS Type Selection
1, "R22", 2,
"407C", 3,
"R134A", 4,
"R410A", 5,
"404A", 6, "507C",
7, "CO2", 8,
"R407A", 9,
"R407F", 10,
"R407F", 11,
"R449A", 12,
"R513A", 13,
"R450A", 14,
"R438A"
LIGHT_UNITS
Light measurement units
0, "FTC", 1, "LUX"
CASE_TYPE
Case Type Selection
0, "Rem Std", 1,
"Rem Dist", 2,
"Self Cont", 3,
"Micro Dist"