FCTL
The Safe-NET system is capable of controlling defrost
activity and scheduling. This menu setting determines
evaporator fan operation during defrost.
1. Selecting DTCL causes the fans to cycle in conjunction
with the defrost termination temperature activated
switch. Fan operation is inverted from the switch
operation to cause the fans to be off during defrost and
on (running) after defrost termination.
2. If NONE is selected, fan control is disabled during
defrost.
3. DFON causes the evaporator fans to run throughout
the defrost cycle
4. DFOF turns the fans off during defrost. The
evaporator fans will resume operation when defrost
terminates from time or temperature or after a preset coil
temperature is reached. This value is set in the setup
(STUP) menu.
Setting this parameter is done in the DEFROST menu.
After navigating to the FCTL submenu, the display will
cycle between FCTL and the current setting. While the
setting is being displayed, press ENTER on the Hand-
Held device or press the SELECT button on the
Safe-NET display module to allow editing of the value.
When the Safe-NET display module begins flashing the
value, use the UP or DOWN arrow keys on the Hand-
Held device or the UP /DOWN buttons on the Safe-NET
display module to change the setting.
Once the desired setting is displayed, press the ENTER
key on the Hand-Held device or the SELECT button on
the Safe-NET display module to store the new value to
NV memory. The display will revert to cycling between
FCTL and the new value.
Note:
At least one coil temperature sensor must be installed for
fan control by coil temperature.
4-33
P/N 0461391A
Hussmann Corporation • Bridgeton, Missouri 63044-2483 U.S.A.
Safe-NET™
DEFR
DTYP
STOP
STRT
FCTL
DCTL
NONE
DFON
DFOF
Value
Menu Structure — FCTL