With 0 displayed, press the ENTER key on the Hand-
Held device or the SELECT button on the Safe-NET
display module. This will store the 0 value to NV
memory. The display will revert to cycling between NSEN
and the new value.
Navigate to the RESET sub menu.
With RST displayed, press the ENTER key on the Hand-
Held device or the SELECT button on the Safe-NET
display module. This will initiate the start up sequence in
the Safe-NET system and scan the new sensor
configuration NV memory.
Note:
Typically this number need not be changed. It should only
be changed when the sensor harness has been replaced or a
new sensor has been added.
The Safe-NET system must be RESET for the new value to
take effect.
Setting the number to a value other than 0 is not
recommended.
LGHT
This setting assigns one of four possible outputs for
control of case lighting.
The Safe-NET system has an optional Relay Board
component that when attached, allows the Safe-NET
display board to control up to four outputs. The
controlled outputs are assigned using the SETUP MENU.
The possible controlled output devices are:
1)
Compressor (CMP)
2)
Evaporator Fans (FANS)
3)
Defrost Heaters (DHTR)
4)
Anti-Sweat Heater (ANTI)
The Safe-NET system, by design, supports four control
outputs. Since not all possible controlled items are valid
in any given configuration, the Light control output is
assigned to an unused output.
Setting this parameter is done in the SETUP menu. After
navigating to the LGHT sub menu item, the display will
cycle between LGHT and the current setting. While the
current value is being displayed, press ENTER on the
Hand-Held device or press the SELECT button on the
Safe-NET display module to allow editing of the value.
When the Safe-NET display module begins flashing the
value, use the UP or DOWN arrow keys on the Hand-
Held device or the UP /DOWN buttons on the Safe-NET
display module to increment or decrement the value to
the desired output.
4-14
P/N 0461391A
MENUS