FSET
The Safe-NET system is capable of controlling defrost
activity and scheduling. When the Safe-NET system is
configured to control evaporator fans during defrost, this
setting provides a temperature set point to resume
evaporator fan operation after defrost cycle termination.
This provides a means to delay activation of the
evaporator fans until the specified coil temperature is
reached. This setting works in conjunction with the
FCTL menu option in the DEFROST MENU. If FCTL
(Fan Control) is disabled, this setting has no effect.
Setting this parameter is done in the SETUP menu. After
navigating to the FSET sub menu item, the display will
cycle between FSET and the current setting. While the
setting is being displayed, press ENTER on the Hand-
Held device or press the SELECT button on the
Safe-NET display module to allow editing of the value.
When the Safe-NET display module begins flashing the
value, use the UP or DOWN arrow keys on the Hand-
Held device or the UP /DOWN buttons on the Safe-NET
display module to change the setting.
Once the desired setting is displayed, press the ENTER
key on the Hand-Held device or the SELECT button on
the Safe-NET display module to store the new value to
NV memory. The display will revert to cycling between
FSET and the new value.
Note:
At least one coil temperature sensor must be installed
4-18
P/N 0461391A
MENUS
Menu Structure — FSET