PRLO
The PRLO parameter sets the low temperature alarm set
point for the product simulator temperature. This set
point and associated alarm is valid for the Safe-NET
system when applied as a Monitoring or Control system.
The configurable range of the LOW alarm is (control set
point)
–
16 ºF.
Setting this parameter is done in the SETUP menu. After
navigating to the PRLO sub menu item, the display will
cycle between PRLO
and the current set point. While the set point is being
displayed, press ENTER on the
Hand-Held device or press the SELECT button on the
Safe-NET display module to allow editing of the value.
When the Safe-NET display module begins flashing the
value,
use the UP or DOWN arrow keys on the Hand-Held
device or the UP /DOWN buttons on the Safe-NET
display module to increment or decrement the value to
the desired set point.
Once the desired set point is displayed, press the ENTER
key on the Hand-Held device or the SELECT button on
the Safe-NET display module to store the new value to
NV memory. The display will revert to cycling between
PRLO and the new value.
Note:
T
he HIGH and LOW alarm settings are limited to +/–
–16
deg F from product simulator temperature set point. Setting
the product simulator set point will not modify the current
alarm settings.They must be set independently to ensure
proper alarming.
A product simulator temperature sensor must be installed
in order to enable associated alarm functions.
4-22
P/N 0461391A
MENUS
Menu Structure — PRLO