36
3.6
Function examples
3.6.1
Display setpoint
PROCEDURE
Press the
>SET key<
[D] and keep it pressed. The setpoint is displayed.
Release the
>SET key<
[D]. The internal temperature is displayed again.
3.6.2
Set/change setpoint
PROCEDURE
Press the
>SET key<
[D] and keep it pressed. The setpoint is displayed.
Use the
>Arrow keys<
[C] to select the required value.
(up) the temperature increases, (down) the temperature decreases.
Release the
>SET key<
[D]. The new setpoint is set.
3.6.3
Changing the Auto-Start function
Following a power outage (or when switching on the temperature control unit), this function can be
used to determine how the temperature control unit is supposed to respond.
Auto-Start function is turned off
The temperature control is started only by manual input when the temperature control unit is
turned on.
Auto-Start function is turned on
The temperature control unit is set to the same state it was in before the power outage. For exam-
ple, before the power outage: Thermoregulation is off; after power outage: Thermoregulation is off.
If temperature control is active during a power outage, the process will automatically continue after
the power outage.
Setting
Display
Description
0
The auto-start function is turned on.
1
The auto-start function is turned off.
PROCEDURE
Press the
>Arrow keys<
[C] and simultaneously for 3 seconds. The display changes from
the display of the temperature to the display of the first menu item.
Press the
>Arrow key<
[C] until the menu item “C40” is displayed.
Press the
>SET key<
[D] and keep it pressed.
Press the
>SET key<
[D] and simultaneously the
>Arrow keys<
[C] and . The display changes
from “0” (auto-start function is ON) to “I” (auto-start function is OFF). Release the
>SET key<
[D]
after the required setting was made.
Press the
>Arrow keys<
[C] and simultaneously for 1 second. Or wait a few seconds after
releasing the
>SET key<
[D]. The selected function is saved and menu is exited. The display shows
the temperature again.
Settings in the menu
item “C40” auto-start
function