Setup mode
OPERATION MANUAL
Chapter 4
Minichiller®
V2.4.0en/09.08.21//1.30
38
4.1.3.2
Setting the overtemperature protection
You need a screwdriver (flat blade 1.0 x 5.5) to set the cut-out value of the overtemperature pro-
tection.
PROCEDURE
Use a screwdriver to set the cut-off value on the potentiometer. The cut-out value must be set to
match the thermal fluid you are using. It is not required to switch on the temperature control
unit.
4.1.4
Testing the overtemperature protection for functionality
Overtemperature protection (OT) does not trip
MORTAL DANGER FROM FIRE
Test the response of the device every month and after each change of the thermal fluid in
order to assure proper functioning.
The steps below are carried out without permanent monitoring of the temperature control unit
DAMAGE TO AND IN THE VICINITY OF THE TEMPERATURE CONTROL UNIT
The following actions may only be carried out while constantly monitoring the temperature
control unit and the application!
The overtemperature protection is installed only in temperature control units that have a heater.
You need a sufficiently large-sized screwdriver to check the overtemperature protection for func-
tionality.
Steps to test the correct functioning of the overtemperature protection:
PROCEDURE
Note down the cut-out value of the overtemperature protection set on the potentiometer.
Switch on the temperature control unit.
Enter a setpoint (room temperature).
→
Start the temperature control process by pressing the
>Start/Stop button<
[E].
Use a screwdriver to set the new cut-off value on the potentiometer. This cut-out value must be
below
the indicated internal temperature. The overtemperature protection is triggered.
Turn off the temperature control unit.
Use a screwdriver to reset the cut-off value on the potentiometer to the original value.
Immediately take the temperature control unit out of operation if the overtemperature protection
is not triggered. Immediately contact Customer Support.
→
. Do
not put the temperature control unit back into operation.
Setting the
cut-out value
Summary of Contents for MPC Minichiller 280
Page 1: ...MPC Minichiller...
Page 2: ......
Page 3: ...OPERATION MANUAL MPC Minichiller...
Page 4: ......
Page 10: ...OPERATION MANUAL Minichiller V2 4 0en 09 08 21 1 30 10...
Page 59: ...Annex Chapter 9 OPERATION MANUAL V2 4 0en 09 08 21 1 30 Minichiller 59 9 Annex...