Make sure there is adequate ventilation (removal of waste heat, fresh air supply) for the tempera-
ture control unit, in case of
air cooling, maintain wall clearance
(see page 18, section
illustrations of the cooling variants«
and page 22, section
).
The liquefier fins must be cleaned (dust) from time to time as only then will the temperature con-
trol unit perform at its maximum cooling capacity.
Identify the position of the ventilation grille, usually located on the front. With some temperature
control units, the ventilation grilles on the side wall, rear or on the underside (table units) of the
temperature control unit.
PROCEDURE
Ventilation grille on the front/rear or on a side wall
Turn off the temperature control unit.
Disconnect the temperature control unit from the power supply.
Remove the ventilation grille to create unhindered access to the liquefier fins.
Clean the liquefier fins using suitable cleaning appliances. Observe the local regulations and
ambient conditions when selecting cleaning appliances.
Make sure the liquefier fins are not damaged or deformed as this will impair the air flow.
Re-mount the ventilation grille after cleaning work.
Connect the temperature control unit to the power supply.
Turn on the temperature control unit.
PROCEDURE
Ventilation grille on the underside (table-top units)
Cleaning of liquefier fins at the underside when the temperature control unit is filled
DAMAGE CAUSED BY THERMAL FLUID PENETRATING THE TEMPERATURE CONTROL UNIT
Empty the temperature control unit before cleaning the liquefier fins at the underside of the
temperature control unit.
Turn off the temperature control unit.
Disconnect the temperature control unit from the power supply.
Drain the thermofluid from the temperature control unit. Additional information is provided on
page 58 in section
»Draining externally open applications«
.
Tilt the temperature control unit to remove the grille (if available) in front of the liquefier fins.
Clean the liquefier fins using suitable cleaning appliances. Observe the local regulations and
ambient conditions when selecting cleaning appliances.
Make sure the liquefier fins are not damaged or deformed as this will impair the air flow.
Re-mount the ventilation grille after cleaning work.
Connect the temperature control unit to the power supply.
Refill the temperature control unit with thermofluid. Additional information is provided on page
56 in section
»Filling and venting externally open application«
.
7.4.4
Clean hat-type strainer (dirt trap) (water-cooled temperature control unit)
Building side isolating valves are not closed
DAMAGE BY ROOM FLOODING
Close the building’s isolating valves in the cooling water supply and return lines.
The strainer at the cooling water inlet must be inspected and cleaned on a regular basis, depend-
ing on water quality.
PROCEDURE
Table-top models:
Turn off the temperature control unit.
Disconnect the temperature control unit from the power supply.
Close the customer’s shut-off valves in the cooling water supply and return lines.