The EPS30-4815AF power system can be configured with two rectifier modules, which are
connected in parallel for output.
shows the mapping between the quantity of rectifier modules in the EPS30-4815AF
power system and the maximum output current.
Table 6-2
Mapping between the quantity of rectifier modules of the EPS30-4815AF power
system and the maximum output current
Quantity of Rectifier Modules
Maximum Output Current
1
15 A
2
30 A
Indicator
describes the indicators on the rectifier module of the EPS30-4815AF power system.
Table 6-3
Indicators on the rectifier module of the EPS30-4815AF power system
Indicator
Status
Description
RUN
Steady green
The rectifier module functions properly.
Off
This indicator is off when the red indicator is
on or the yellow indicator is on (not caused by
output overcurrent).
ALM
Steady yellow
The ALM indicator of the rectifier module is
valid when PS-off, OTP, and primary
protection are valid, or when overcurrent
occurs.
Blinking yellow
The communication of the rectifier module is
interrupted.
Off
The rectifier module functions properly.
FAULT
Steady red
The FAULT indicator of the rectifier module
is valid when PS-enable and Vo-OV are valid,
or when fan fault, no output, or output short
circuit occurs.
Off
The rectifier module functions properly.
describes the indicators on the monitoring module of the EPS30-4815AF power
system.
UA5000 Universal Access Unit
Environment Monitoring
6 EPS30-4815AF Monitoring Solution
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential