huawei(config-if-power4875l-0)#
power battery-test auto-test off-test forbid
time-test permit 180 1
10. Configure the rectifier unit parameter.
huawei(config-if-power4875-0)#
power module-num 2 1 2
11. Configure the load and battery high-temperature power-off parameters.
huawei(config-if-power4875l-0)#
power temperature-off load-off-state forbid
load-off-temperature 70 battery-off-state permit battery-off-temperature 53
12. Configure the environment temperature parameters.
huawei(config-if-power4875l-0)#
power environment temperature 68 -5 80 -20
13. Configure the extended digital parameters.
huawei(config-if-power4875l-0)#
power outside_digital 0 available-level low-
level name Fan
huawei(config-if-power4875l-0)#
power outside_digital 1 available-level low-
level name HABF_FAN
huawei(config-if-power4875l-0)#
power outside_digital 3 available-level low-
level name SPD
huawei(config-if-power4875l-0)#
power outside-digital 5 available-level low-
level name HEX
huawei(config-if-power4875l-0)#
power outside-digital 6 available-level low-
level name MDF-door
14. Query the information about the configured parameters and environment parameters of the
power system.
huawei(config)#
interface emu 0
huawei(config-if-power4875l-0)#
display power system parameter
EMU ID: 0 Power system information
----------------------------------------------------------------------------
charge control state : automatic control
equalizing Voltage : 56.500V floating Voltage: 53.500V
charge lmt quotiety: 0.150 equalizing time : 60 days
battery number : 1
battery 0 capacity : 150 AH
battery temperature test upper : 80C battery temperature test lower: -20C
temperature redeem quotiety : 80mV
battery temperature alarm upper: 50C battery temperature alarm lower: 0C
load off permit : forbid load off voltage : 44.000V
battery off permit : permit battery off voltage : 43.000V
AC over alarm voltage : 280V AC lack alarm voltage : 180V
DC over alarm voltage : 58 V DC lack alarm voltage : 45V
power module number: 2
module 0 address: 1 module 0 switch state : On
module 1 address: 2 module 1 switch state : On
Load high-temperature-off permit: forbid
Load high-temperature-off temperature(C): 70
Battery high-temperature-off permit: permit
Battery high-temperature-off temperature(C): 53
----------------------------------------------------------------------------
huawei(config-if-power4875l-0)#
display power environment parameter
EMU ID: 2 Power environment configration
parameter
----------------------------------------------------------------------------
AnalogID Name AlmUpper AlmLower TestUpper TestLower Unit
Type
0 Temperature 68 -5 80 -20 C
Current
----------------------------------------------------------------------------
DigitalID Name Level |DigitalID Name
Level
0 Fan 0 | 1 HABF_FAN
0
2 - 0 | 3 SPD
1
4 - 1 | 5 HEX
UA5000 Universal Access Unit
Environment Monitoring
8 ETP4890 Monitoring Solution
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
148