Item
Data Plan for the
F01D500 Cabinet
Remarks
Lower temperature
threshold of the battery
set: -20°C
This parameter is set according to the actual
requirements.
Default: -20°C.
Temperature
compensation
coefficient of the battery
set: 80 mV
This parameter is set according to the actual
requirements. The temperature compensation
coefficient refers to the variable of the float
charging voltage of the battery set when the
temperature of the battery set changes by every 1°
C.
Default: 80 mV.
Power
supply load
power-off
and battery
set power-off
parameters
Load power-off
permission status: forbid
This parameter is set according to the actual
requirements.
Default: forbid.
Battery set power-off
permission status: permit
This parameter is set according to the actual
requirements.
Default: permit.
Load power-off voltage:
44 V
This parameter is set according to the actual
requirements.
Default: 44 V.
Battery set power-off
voltage: 43 V
This parameter is set according to the actual
requirements.
Default: 43 V.
Power
distribution
parameters
AC overvoltage alarm
threshold of the power
supply: 280 V
This parameter is set according to the actual
requirements. When the AC voltage exceeds the
preset overvoltage alarm threshold, the system
reports an AC overvoltage alarm. In this case, the
rectifier unit powers off automatically to protect
the system.
Default: 280 V.
AC undervoltage alarm
threshold of the power
supply: 180 V
This parameter is set according to the actual
requirements. When the AC voltage falls below
the preset undervoltage alarm threshold, the
system reports an AC undervoltage alarm. In this
case, the rectifier unit powers off automatically to
protect the system.
Default: 180 V.
UA5000 Universal Access Unit
Environment Monitoring
8 ETP4890 Monitoring Solution
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
141