7.5 Configuring the Environment Monitoring Parameters of
the EPS75-4815AF
This topic describes how to configure the environment monitoring parameters of the
EPS75-4815AF through the CLI.
Mapping Between Monitoring Parameters and Device Ports
describes the mapping between the monitoring parameters displayed on the sensor
transfer box.
Table 7-19
Mapping between the monitoring parameters displayed on the host and the ports on
the sensor transfer box
Monito
ring
Parame
ter
Displa
yed on
the
Host
Devic
e Port
Applicatio
n in the
F02A
Cabinet
Application
in the
F02AF
Cabinet
Applicati
on in the
F01D200
Cabinet
Applicati
on in the
F01D500
Cabinet
Applicati
on in the
F01D1000
Cabinet
Digital
0
JTD1
Fan
monitoring
board of the
HABA shelf
Fan
monitoring
board of the
HABD shelf
Fan
monitoring
board of
the HABD
shelf
Fan
monitoring
board of
the HABD
shelf
Fan
monitoring
board of
the HABD
shelf
Digital
1
JTD2
Fan
monitoring
board of the
HABA shelf
Fan
monitoring
board of the
HABF shelf
Not
connected
by default,
used to add
a user-
defined
monitoring
digital
parameter
Fan
monitoring
board of
the HABF
shelf
Fan
monitoring
board of
the HABF
shelf
Digital
2
JTD3
Not
connected by
default, used
to add a user-
defined
monitoring
digital
parameter
Not
connected by
default, used
to add a user-
defined
monitoring
digital
parameter
Not
connected
by default,
used to add
a user-
defined
monitoring
digital
parameter
Not
connected
by default,
used to add
a user-
defined
monitoring
digital
parameter
Fan
monitoring
board of
the HABD
shelf in the
right
device
compartme
nt
UA5000 Universal Access Unit
Environment Monitoring
7 EPS75-4815AF Monitoring Solution
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
107