battery temperature test upper : 80C battery temperature test lower: -20C
temperature redeem quotiety : 80mV
battery temperature alarm upper: 50C battery temperature alarm lower: 0C
load off permit : forbid load off voltage : 44.000V
battery off permit : permit battery off voltage : 43.000V
AC over alarm voltage : 280V AC lack alarm voltage : 180V
DC over alarm voltage : 58 V DC lack alarm voltage : 45V
power module number: 5
module 0 address: 1 module 0 switch state : On
module 1 address: 2 module 1 switch state : On
module 2 address: 3 module 2 switch state : On
module 3 address: 4 module 3 switch state : On
module 4 address: 5 module 4 switch state : On
Load high-temperature-off permit: forbid
Load high-temperature-off temperature(C): 65
Battery high-temperature-off permit: forbid
Battery high-temperature-off temperature(C): 53
----------------------------------------------------------------------------
huawei(config-if-power4875l-0)#
display power environment parameter
EMU ID: 2 Power environment configration
parameter
----------------------------------------------------------------------------
AnalogID Name AlmUpper AlmLower TestUpper TestLower Unit
Type
0 Temperature 50 0 80 -20 C
Current
----------------------------------------------------------------------------
DigitalID Name Level |DigitalID Name
Level
0 - 1 | 1 -
1
2 - 1 | 3 -
1
4 - 1 | 5 -
1
6 -
1
----------------------------------------------------------------------------
The results show that the power, temperature, and humidity parameters have been
configured automatically in the system; however, certain parameters need to be modified,
and certain extended monitoring parameters need to be added.
4.
Configure the battery charging parameters.
If the planned data is the same as the query result, the parameters need not be configured.
If the parameters need to be modified, run the
power charge
command.
5.
Configure the battery management parameters.
huawei(config-if-power4875l-0)#
power battery parameter 0.15 60 1 150
6.
Configure the temperature compensation coefficient of the battery.
If the planned data is the same as the query result, the parameters need not be configured.
If the parameters need to be modified, run the
power battery temperature
command.
7.
Configure the power supply load power-off and battery set power-off parameters.
If the planned data is the same as the query result, the parameters need not be configured.
If the parameters need to be modified, run the
power off
command.
8.
Configure the power distribution parameters.
If the planned data is the same as the query result, the parameters need not be configured.
If the parameters need to be modified, run the
power supply-parameter
command.
9.
Configure the battery discharging test parameters.