Smoke Sensor
Type
Specification
No smoke is detected.
Smoke is detected.
Voltage type
Output voltage > 5 V
Output voltage < 3.3 V
Dry-contact type
Disconnected
Connected
10.2 Installing the Sensors
This section describes how to install the sensors that are provided by Huawei. For those sensors
not provided by Huawei, refer to their installation guide accordingly.
10.2.1 Installation Position
This topic describes the installation positions of sensors.
Install sensors in suitable positions so that they can work properly.
lists the
installation position for each type of sensor.
Table 10-17
Installation position for each type of sensor
Sensor
Installation Position
Water sensor
A position where water can flow into easily or a low position.
Smoke sensor
In the middle of the ceiling or at the top of the equipment compartment in
the cabinet.
Door status
sensor
The joint between the upper edge of the door frame and the door.
Temperature
and humidity
sensor
A position where the air flows smoothly, with the flowing speed ranging
from 0.1 m/s to 1 m/s, for example, at the top of the equipment compartment
in the cabinet.
Main
distribution
frame (MDF)
sensor
-
surge
protector
sensor
-
Battery
Temperature
Sensor
Install the temperature probe at a position that best represents the
temperature in the battery compartment, and do not connect the probe with
other heating devices.
Over/Under-
voltage
protection
module
Install the module before the AC power distribution.
UA5000 Universal Access Unit
Environment Monitoring
10 Sensors
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
192