Parameter
Setting Guide
Default Value
Rotation
time
0 by default
0
Forced
rotation
This item is set to No by
default. If forced rotation
is required, the function
is set to Yes.
No
Requirement
control
Anti-competitive
running is recommended
for the following
scenario: In one
teamwork, the
temperature and
humidity control type
and temperature and
humidity set point of
units are the same, and
device heat loads are
distributed evenly.
Disable
Cascade
function
If the heat load to the
device increases, the
cascade function is
recommended.
Disable
Differential
pressure
sharing
This parameter can be
enabled when there are
at least two smart
cooling products in the
group are configured
with differential pressure
sensors.
Disable
Cold aisle
temperature
and humidity
sharing
This parameter can be
enabled when there are
at least two smart
cooling products in the
group are configured
with cold aisle T/H
sensors.
Disable
Hot aisle
temperature
and humidity
sharing
This parameter can be
enabled when there are
at least two smart
cooling products in the
group are configured
with hot aisle T/H
sensors.
Disable
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual