Alar
m ID
Alarm
Severit
y
Alarm Name
Probable Cause
Solution
A172
-01
MAJOR
SPD and
voltage
detection
board comm
failed
1. The
communications
cable is not
connected properly.
2. The SPD and
voltage detection
board is faulty.
3. The
communications
port of the main
control board is
faulty.
1. Check the
communications cable.
2. Replace the SPD and
voltage detection
board.
3. Maintain or replace
the main control
board.
A172
-01
MAJOR
Backup SPD
and volt
detection
board comm
failed
1. The
communications
cable is not
connected properly.
2. The SPD and
voltage detection
board is faulty.
3. The
communications
port of the main
control board is
faulty.
1. Check the
communications cable.
2. Replace the SPD and
voltage detection
board.
3. Maintain or replace
the main control
board.
A174
-01
MAJOR
SPD function
failure
The SPD and
voltage detection
board is faulty.
1. Replace the SPD and
voltage detection
board.
A174
-01
MAJOR
Backup SPD
function
failed
The SPD and
voltage detection
board is faulty.
1. Replace the SPD and
voltage detection
board.
A174
-02
MAJOR
SPD function
failure
1. The SPD is faulty.
2. The cable to the
SPD is not
connected properly.
1. Replace the SPD.
2. Check the cable
connection to the SPD.
A184
-01
WARNI
NG
Compressor 1
preheating
alarm
The compressor is
preheating.
1. Power on the device
after the compressor
has preheated.
A184
-01
WARNI
NG
Compressor 2
preheating
alarm
The compressor is
preheating.
1. Power on the device
after the compressor
has preheated.
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
6 System Operation and Maintenance
Issue 06 (2020-08-19)
Copyright © Huawei Technologies Co., Ltd.
164