NO TICE
Before replacing the water pump, drain water from the water pan completely.
Procedure
Step 1 On the controller home screen, tap Shutdown, and turn off the device switch in
the PDC.
NO TICE
Exercise caution because the device is still energized after it is shut down on the
controller home screen.
Step 2 Open the no.2nd maintenance door and disconnect the terminal of the water
pump power cable.
Step 3 Remove the water pump.
1. Remove the inlet and outlet pipes of the water pump.
Figure 6-12 Removing the flange assembly
2. Remove the fastener from the water pump using a socket wrench, and pull
out the spray pump.
Step 4 Install a new spray pump on the device, install the flange assembly at the inlet
and outlet of the water pump, and close the maintenance door.
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
6 System Operation and Maintenance
Issue 06 (2020-08-19)
Copyright © Huawei Technologies Co., Ltd.
217