Task
Baseline Requirement
Troubleshooting
The air filter is not damaged
or distorted.
Replace the air filter.
Y-shaped
strainer
The Y-shaped strainer is not
blocked.
Remove the air filter of the Y-
shaped strainer in shutdown mode,
exhaust water from pipes and
clean the air filter.
Water
tank
The float has no scale.
Clean up the scale from the float.
The water tank filter is not
blocked.
Remove the air filter from the
water tank in the shutdown state,
clean it with water, and reinstall it.
Compresso
r
The compressor is secured.
Tighten screws if the compressor is
not secured.
The compressor service valve
has no oil stains.
Clean the oil stains.
The operating compressor
generates no metal friction
noise or collision noise from
inside.
Replace the compressor.
Pipe
The refrigerant pipe does not
leak or corrode, and the
wrapped thermal insulation
foam is intact.
Repair the leakage points and
rewrap thermal insulation foam.
Wear protective gloves and
touch the compressor angle
valve (Only for NetCol8000-
E220DM0BA), needle valve,
and soldering points in the
refrigerant pipe to check
whether there are oil stains.
If there is an oil stain, check
whether the suction and exhaust
pressure of the compressor is
within the normal ranges. (For the
proper ranges of suction and
exhaust pressure of the
compressor, If the pressure is
beyond the normal range, contact
Huawei technical support.
No water exists under the
water pipe or on the thermal
insulation foam.
● If drops of water are evenly
distributed, wipe off them with
a dry cloth.
● If there are large water marks,
close the water inlet sluice and
process the leak points. If the
thermal insulation foam is
damaged or missing, lay out
new thermal insulation foam.
The refrigerant pipe support
is secure and intact.
Replace the refrigerant pipe
support and secure it again.
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
6 System Operation and Maintenance
Issue 06 (2020-08-19)
Copyright © Huawei Technologies Co., Ltd.
122