Symptom
Possible Cause
Solution
The motor specifications
do not meet the
requirements (voltage).
Replace the motor.
The motor is poorly
insulated.
Replace the motor.
The running sound is
abnormal.
The compressor, fan, or
pipes are loose.
Check and secure loose
parts.
The compressor does not
work.
The high pressure switch
is triggered.
Check the high pressure
switch.
The circuit breaker, fuse,
or cable is disconnected.
Check the main circuit
breaker, compressor
circuit breaker, fuses, and
cables.
The compressor motor is
damaged.
Check whether the
motor is damaged and
needs replacing.
The compressor does not
require starting.
Check for the
requirement status on
the LCD.
The drive is faulty.
Replace the drive.
The compressor
discharge temperature is
too high.
The refrigerant loop or
component is blocked.
Clean foreign matters
from the refrigerant
loop.
Air enters the refrigerant
loop.
Exhaust air and repair
the pipeline.
Heat dissipation is poor
because the condenser is
dirty or blocked.
Clean the condenser fins.
The exhaust fan fails.
Check whether the
exhaust fan works
properly.
The refrigerant is
insufficient.
Charge more refrigerant.
The compressor
discharge pressure is too
low.
The exhaust fan speed
controller fails.
Replace the fan speed
controller.
The refrigerant is
insufficient.
Charge more refrigerant.
Refrigerant leaks.
Check the pipeline for
leakage.
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
6 System Operation and Maintenance