Alar
m ID
Alarm
Severit
y
Alarm Name
Probable Cause
Solution
A306
-01
MAJOR
Spray
function
abnormal
1. The spray pump
inlet is blocked.
2. The spray pump
is air-sealed.
3. The cable to the
spray pump is not
connected properly.
4. The spray pump
is faulty.
5. The cable to the
spray water flow
switch is not
connected properly.
6. The spray water
flow switch is faulty.
7. The float does
not drop because
the spray low float
is faulty.
1. Clear the blockage
from the spray pump
inlet.
2. Remove the air from
the spray pump.
3. Check the cable
connection to the spray
pump.
4. Replace the spray
pump.
5. Check the cable
connection to the spray
water flow switch.
6. Maintain the spray
water flow switch.
7. Maintain the spray
low float.
A306
-02
MAJOR
Spray
function
abnormal
1. The spray pump
inlet is blocked.
2. The spray pump
is air-sealed.
3. The cable to the
spray pump is not
connected properly.
4. The spray pump
is faulty.
5. The cable to the
spray water flow
switch is not
connected properly.
6. The spray water
flow switch is faulty.
7. The float does
not drop because
the spray low float
is faulty.
1. Clear the blockage
from the spray pump
inlet.
2. Remove the air from
the spray pump.
3. Check the cable
connection to the spray
pump.
4. Replace the spray
pump.
5. Check the cable
connection to the spray
water flow switch.
6. Maintain the spray
water flow switch.
7. Maintain the spray
low float.
A307
-01
WARNI
NG
Spray water
pump 1
exceed
runtime
alarm
The accumulated
runtime the spray
pump exceeds the
alarm threshold.
1. Replace the pump
and clear the
accumulated runtime.
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
6 System Operation and Maintenance
Issue 06 (2020-08-19)
Copyright © Huawei Technologies Co., Ltd.
203