167
Alarm
ID
Alarm Name
Alarm
Severity
Impact
Possible Causes
Solution
2.
The T/H sensor
is faulty.
a113
Hot-aisle 1/2/3
T/H brd comm
failed
Major
The alarm is
generated.
1.
The cables to
the T/H sensor
are loose or
damaged.
2.
The DIP switch
of the T/H
sensor is set
incorrectly.
3.
The T/H sensor
is faulty.
4.
The
communication
port of the
control board is
faulty.
1.
Check the cables to the
T/H sensor.
2.
Set the DIP switch of the
T/H sensor correctly.
3.
Maintain or replace the
T/H sensor.
4.
Maintain or replace the
control board.
a116
iCooling
communication
fault
Major
The alarm is
generated, and
the iCooling
function is
disabled.
1.
The supervisory
(ECC) is faulty.
2.
The ETH
converter is
faulty.
3.
The smart
socket is faulty.
4.
The cables are
faulty between
the smart
cooling product
and the ETH
converter or the
supervisory.
1.
Check the supervisory
works properly.
2.
Check the ETH converter
works properly.
3.
Check smart socket works
properly.
4.
Maintain or replace the
cables between the smart
cooling product and the
ETH converter or the
supervisory.
a117
Group units
number not
match
Major
Cannot obtain
smart cooling
product data
from the micro
module, and
the iCooling
mode cannot
be started.
1.
Teamwork
settings are
incorrect for
slave units.
2.
Teamwork
settings are
incorrect for the
master unit.
3.
Slave unit
dropped.
4.
The ETH
converter is
faulty.
5.
The smart
socket is faulty.
6.
The cables are
faulty between
the smart
1.
Modify teamwork settings
for slave units to enable
slave units to join the
teamwork group.
2.
Set Total number of units
on the master unit to the
actual number of units.
3.
Check slave unit's
Teamwork Wire
connection and Running
Condition.
4.
Check the ETH converter
works properly.
5.
Check smart socket works
properly.
6.
Maintain or replace the
cables between the smart
cooling product and the