NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
6 System Operation and Maintenance
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
160
Alarm
ID
Alarm Name
Alarm
Severity
Impact
Possible Causes
Solution
HP lock
the compressor
is shut down.
The alarm can
be manually
cleared.
alarm is generated
frequently.
alarm.
NOTE
After the alarm is rectified, click
Manual clear
on the alarm page.
a059
Suction
pressure sensor
fault
Major
The alarm is
generated.
1.
The cables to
the press sensor
are loose or
damaged.
2.
The press
sensor is faulty.
1.
Check the cables to the
press sensor.
2.
Replace the press sensor.
a060
Comp suction
LP
Major
The alarm is
generated, and
the compressor
is shut down.
1.
The refrigerant
leaks.
2.
The solenoid
valve is faulty.
3.
The cables to
the press sensor
are loose or
damaged.
4.
The press
displayed is
different from
the actual press.
5.
The dryer filter
is blocked.
6.
The expansion
valve is
blocked.
7.
The indoor fans
are faulty.
1.
Check for any leakages.
Fill refrigerant after
maintenance or
replacement.
2.
Maintain or replace the
solenoid coil or the
solenoid valve.
3.
Check the cables to the
press sensor.
4.
Calibrate or replace the
press sensor.
5.
Maintain or replace the
dryer filter.
6.
Maintain or replace the
expansion valve.
7.
Maintain or replace the
indoor fans.
a061
Comp suction
LP lock
Critical
The alarm is
generated, and
the compressor
is shut down.
The a060 comp
suction LP alarm is
generated
frequently.
Reference to the solutions for
the a060 comp suction LP
alarm.
NOTE
After the alarm is rectified, click
Manual clear
on the alarm page.
a062
Comp drive
alarm
Major
The alarm is
generated, and
the compressor
is shut down.
1.
The comp
driver is faulty.
2.
The comp is
faulty.
1.
Maintain or replace the
comp driver.
2.
Maintain or replace the
comp.
NOTE
After the alarm is rectified, click
Manual clear
on the alarm page.
a063
Comp drive
comm failed
Critical
The alarm is
generated, and
the compressor
is shut down
(the
1.
The cables to
the comp driver
are loose or
damaged.
2.
The comp
1.
Check the cables to the
comp driver.
2.
Maintain or replace the
comp driver.
3.
Turn on the air switch of
Summary of Contents for NetCol5000-A021