6 System Operation and Maintenance
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
208
Figure 6-21
Removing a module
Step 4
Take out the handle and pull out the module from the subrack, as shown by (2) in
When installing a new module, ensure that the handle is in the upper part of the module, and
the HUAWEI logo is in the lower left corner of the module.
Step 5
Insert the spare module into the corresponding slot, and flip the clip upwards to lock the
module.
Step 6
Install the air filter and close the rear door.
----End
6.5.12 (Optional) Replacing the Liquid Level Detector
Prerequisites
The liquid level detector needs to be replaced.
A spare liquid level detector of the same model is available and functional.
Tool: Phillips screwdriver
Context
Components and working principle: A liquid level detector is composed of the conductor
outer jacket, liquid level detector, switch, and card pole. A liquid level detector rises or drops
as the liquid level changes due to the magnetism of the liquid level switch, causing the reed
switch chip in the specified position inside the sensor detection pipe to move and send the
contact on/off conversion signal to control the liquid level detector.
The liquid level detector can be maintained only from the front.