NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
6 System Operation and Maintenance
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
161
Alarm
ID
Alarm Name
Alarm
Severity
Impact
Possible Causes
Solution
compressor
responds to
system
requirements
10s after the
communication
failure alarm is
cleared).
driver is faulty.
3.
The air switch
of comp driver
is off.
comp driver.
a064
Comp drive
lock
Critical
The alarm is
generated, and
the compressor
is shut down.
The comp shuts
down due to the
driver fault for
multiple times.
Check whether other alarms of
the comp driver are generated.
NOTE
After the alarm is rectified, click
Manual clear
on the alarm page.
a065
Comp drive DC
overvolt
Major
The alarm is
generated.
1.
The power
supply voltage
is high.
2.
The comp
driver is faulty.
3.
The comp is
faulty.
1.
Check the power supply
voltage.
2.
Maintain or replace the
comp driver.
3.
Maintain or replace the
comp.
a066
Comp drive DC
undervolt
Major
The alarm is
generated.
1.
The power
supply voltage
is low.
2.
The comp
driver is faulty.
3.
The comp is
faulty.
4.
The main
power supply is
faulty or the
cables to the
comp driver are
loose or
damaged.
1.
Check the power supply
voltage.
2.
Maintain or replace the
comp driver.
3.
Maintain or replace the
comp.
4.
Reconnect the main power
supply or the cables to the
comp driver.
a067
Comp drive
overload
Major
The alarm is
generated.
1.
The comp is in
lack of oil.
2.
The condenser
fins are
blocked.
3.
The outdoor
units do not run
properly.
4.
The refrigerant
is overfilled.
5.
The comp is
faulty.
1.
Fill oil to the comp.
2.
Clean the condenser fins.
3.
Maintain or replace the
outdoor units.
4.
Decrease certain amount of
refrigerant.
5.
Maintain or replace the
comp.
a068
Comp drive
overcurrent
Major
The alarm is
generated.
1.
The comp is in
lack of oil.
1.
Fill oil to the comp.
2.
Clean the condenser fins.