NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
4 ACC Introduction
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
99
Parameter Description
Configuration
Principle
Default Value
changes, select the
corresponding
networking mode on the
screen. If the networking
mode is changed on the
screen, the software will
restart and then run in the
new networking mode.
Total
number of
units
Number of the smart
cooling products in this
group (1 to 32 can be
set).
Total number of the
smart cooling products in
this group.
3
Number of
running
units
Number of active units in
a group. The value
ranges from 1 to
Total
number of units
.
The master unit assigns
the devices to be active
units by the device
number, beginning with
the address 1 until to
Number of running
units
. The rest will
become the standby
ones.
2
Rotation
Disable or enable the
active and standby smart
cooling products to
change identity after a
certain time, maximizing
their service life.
This function is
recommended when the
heat is even.
Disable
Rotation
period
Rotation days (1–30).
7 by default.
7 day(s)
Rotation
time
24 hours in a day (0–23).
0 by default.
0
Forced
rotation
Forced rotation
specifies whether to
enable a forcible rotation
on the group before the
specified rotation time.
After a forced rotation,
the accumulated time is
recalculated.
This item is set to
No
by
default. If forced rotation
is required, the function
is set to
Yes
.
No
Requiremen
t control
Enable or disable the
requirement control for
the master device.
When the requirement
control is
Enable
, the
master device
synchronizes data (the
temperature and
The requirement control
function is recommended
for the following
scenario: In one
teamwork, the
temperature and
humidity control type
and temperature and
Disable