NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
3 Installation Guide
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
78
Outdoor unit signal cables can be connected over RS485 (default) or dry contacts. In
RS485 connection mode, the indoor unit can obtain the operating status and alarm
information of the outdoor unit and control the rotational speed and on/off status of the
outdoor unit. In dry contact connection mode, the indoor unit can only control the on/off
status of the outdoor unit. If dry contact connection is used, choose
Settings
>
System
Settings
>
Outdoor Fan
and set Outdoor fan control mode to
Dry contact
.
If the signal cable connects to a dry contact while
Outdoor fan control mode
is set to
Communicate
, the
Outdoor fan communication failure
alarm will be displayed on the
LCD.
If the signal cable connects to an RS485 port while
Outdoor fan control mode
is set to
Dry contact
, the
Comp discharge HP
alarm will be displayed on the LCD after the
compressor starts.
If the
Outdoor fan control mode
is changed on the screen, the monitoring software will
restart.
Procedure
Step 1
Route the cable through the cable protection ring on the top or bottom from the outside, then
through the cable hole on the top or bottom of the electric control box along the outside of the
electric control box.
Step 2
Connect signal cables.
(RS485 connection) Connect one end of the cable to points 1, 2, and 3 on the external
signal port X302 and the other end to ports 3, 4, and 5 on the outdoor unit.
shows the signal cable route.
(Dry contact connection) Connect one end of the cable to points 1 and 2 on the external
signal port X301 and the other end to ports 1 and 2 on the outdoor unit.
shows the signal cable route.
Step 3
Secure the cable using cable ties.
----End
3.11.4.3 Connecting the Water Sensor Cable
Procedure
Step 1
Connect one end of the water sensor cable to a water sensor.
Step 2
Connect the other end of the water sensor cable to points 7 and 8 on the external signal port
X301.
shows the route of the water sensor signal cable.
Step 3
Secure the water sensor cable to the cabinet using cable ties.
----End