5 Power-On Commissioning
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
136
5.2.4 Partially Charging in Refrigerant
Prerequisites
Before refrigerant charging, ensure that the air is exhausted from the hose connecting to the
steel vessel of the refrigerant.
Context
Wear protective gloves when handling refrigerant.
Charge the refrigerant (R410A) after checking that the cooling system does not leak and
the vacuum meets the requirements.
Charge refrigerant as required upon calculation shown in
Refrigerant and Refrigerant Oil to Be Charged
. Otherwise, the device may be damaged.
Procedure
Step 1
Replace the vacuum pump with the steel vessel of liquid refrigerant, as shown in