NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
4 ACC Introduction
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
117
Procedure
Step 1
On the home screen, choose
Maint
>
Performance Maint
Figure 4-29
Performance maint screen
Step 2
Tap
Clear
of a specific performance parameter to clear its runtime.
----End
4.4.2.5 Calibrating a Sensor
Context
Calibrate a sensor if the displayed temperature or humidity on the sensor deviates from the
actual value. For example, if the return air temperature measured by other temperature
detection devices at the return air detection point is 20°C while the value measured by the
sensor is 22°C, the sensor has an error of 2°C, and the calibration value should be set to –2°C.
Procedure
Step 1
On the home screen, choose
Maint
>
Sensor Adjust
Figure 4-30
Sensor adjust screen
Step 2
Fill the calibration value based on the measured error.
----End
Summary of Contents for NetCol5000-A021
Page 234: ......