Installing FRUs
106
2.
Enter the
slotShow
command.
The command output should show the new CP card as
enabled
.
3.
Determine the firmware version by entering the
firmwareShow
command.
4.
If the firmware version of the replacement card does not match that of the active CP card,
bring the replacement card to the same firmware level as the active card. Check with the
switch supplier for supported versions.
Download the firmware, using either of the following command options:
•
firmwareDownload
to download the firmware to both CP cards at the same time.
Enter all requested information and choose the
reboot
option.
•
firmwareDownload -s
to download the firmware to only one of the CP cards. Enter
all requested information and choose the
reboot
option.
swDir:admin> slotShow
Slot Blade Type ID Status
---------------------------------
1 SW BLADE 4 FAULTY
2 SW BLADE 4 DISABLED
3 SW BLADE 4 ENABLED
4 SW BLADE 4 DIAG RUNNING POST2
5 CP BLADE 5 ENABLED
6 CP BLADE 5 ENABLED
7 UNKNOWN VACANT
8 SW BLADE 4 DIAG RUNNING POST1
9 SW BLADE 4 INSERTED, NOT POWERED ON
10 UNKNOWN VACANT
swDir:admin>
swDir:admin> firmwareshow
Primary partition: v4.2.0meteor_pit_02_031204_0722
Secondary Partition: v4.2.0meteor_pit_02_031204_0722
swDir:admin>