Specify Grounding Requirements
47
Specify Grounding Requirements
Grounding systems
HP rp7400 servers require two methods of grounding:
•
Power distribution safety grounding
•
High frequency intercabinet grounding
NOTE
Some of the grounding requirements described here may differ outside of North America.
Power distribution safety grounding
The power distribution safety grounding system consists of connecting various points in the power
distribution system to earth ground using green (green/yellow) wire ground conductors. Having these ground
connections tied to metal chassis parts that may be touched by computer room personnel protects them
against shock hazard from current leakage and fault conditions.
Power distribution systems consist of several parts. Hewlett-Packard recommends that these parts be solidly
interconnected to provide an equal-potential ground to all points.
Main building electrical ground
The main electrical service entrance equipment should have an earth
ground connection, as required by applicable codes. Connections such as a grounding rod, building steel, or a
conductive type cold water service pipe provide an earth ground.
Electrical conduit ground
All electrical conduits should be made of rigid metallic conduit, Flex-T conduit,
or liquid-tight conduit that is securely connected together or bonded to panels and electrical boxes, so as to
provide a continuous grounding system.
Power panel ground
Each power panel should be grounded to the electrical service entrance with green
(green/yellow) wire ground conductors. The green (green/yellow) wire ground conductors should be sized per
applicable codes (based on circuit over current device ratings).
Computer equipment ground
Ground all computer equipment with the green (green/yellow) wire
included in the branch circuitry. The green (green/yellow) wire ground conductors should be connected to the
appropriate power panel and should be parity-sized (based on circuit over current device ratings).
Cabinet interconnect grounding
Signal interconnect between system cabinets requires high frequency ground return paths. Connect all
cabinets to site ground.
NOTE
In some cases power distribution system green (green/yellow) wire ground conductors are too
long and inductive to provide adequate high frequency ground return paths. Therefore, the
customer may choose to provide a ground strap for connecting the system cabinet to the site
grounding grid (customer-supplied). Installation of this ground strap is optional and there is a
chance that it may cause ground loops.
Power panels located in close proximity to the computer equipment should also be connected to site grounding
grid. Methods of providing a sufficiently high frequency ground grid are described in the next sections.
Summary of Contents for rp7400
Page 1: ...rp7400 Hardware Manual ...
Page 4: ...What s New 4 ...
Page 6: ...System Overview 6 ...
Page 15: ...rp7400 Enterprise Server System Safety and Regulatory Information 15 ...
Page 16: ...rp7400 Enterprise Server System Safety and Regulatory Information 16 ...
Page 17: ...rp7400 Enterprise Server System Safety and Regulatory Information 17 ...
Page 22: ...rp7400 Enterprise Server System Safety and Regulatory Information 22 ...
Page 24: ...Review the Sales Order 24 ...
Page 26: ...Plan the Site Visit 26 ...
Page 28: ...Visit the Site 28 ...
Page 32: ...Review HP Responsibilities 32 ...
Page 36: ...Develop the Schedule 36 ...
Page 38: ...Specify the Space for Unpacking 38 ...
Page 44: ...Specify Hard Floor Requirements 44 ...
Page 52: ...Specify the System Requirements 52 ...
Page 56: ...Determine the ESD Requirements 56 ...
Page 58: ...Determine the Acoustic Requirements 58 ...
Page 60: ...Determine RFI Requirements 60 ...
Page 62: ...Review Local Codes 62 ...
Page 64: ...Determine Altitude Requirements 64 ...
Page 68: ...Identify Sources of Electrical Interference 68 ...
Page 70: ...Identify Other Environmental Influences 70 ...
Page 72: ...Identify Telephone Requirements and Define Remote Access 72 ...
Page 74: ...Identify Special Network Requirements 74 ...
Page 76: ...Determine Service Access Needs 76 ...
Page 78: ...Determine Fire Protection Requirements 78 ...
Page 80: ...Define E Stop Requirements 80 ...
Page 82: ...Determine Other Needs 82 ...
Page 84: ...Generate the Plan 84 ...
Page 86: ...Review the Plan With the Customer 86 ...
Page 88: ...Execute the Site Plan 88 ...
Page 94: ...Console Cable Connections 94 ...
Page 96: ...HP 700 Series System Console Configuration 96 ...
Page 100: ...Core I O Connections and Indicators 100 ...
Page 104: ...Secure Web Console Installation 104 ...
Page 106: ...LAN Console 106 ...
Page 108: ...PC Direct Connect as System Console 108 ...
Page 114: ...SCSI Devices 114 ...
Page 118: ...Cable Management 118 ...
Page 124: ...Cabinet Extension Kit 124 ...
Page 134: ...rp7400 Server Boot up 134 ...
Page 136: ...Accessing Guardian Service Processor Internal Port 136 ...
Page 142: ...Chapter Shutting Down the SPU Shutting Down the SPU 2 ...
Page 148: ...Adding a Disk Drive to an HP UX System 146 ...
Page 162: ...Add I O Cards 160 ...