MAN1032-10-EN_EXL6_UserManual
March 12, 2020
179 | 191
CHAPTER 23: TROUBLESHOOTING / TECHNICAL SUPPORT
23.1 Connecting to the EXL6 OCS
Cscape connects to the local controller automatically when the serial connection is made. The
status bar below shows an example of a successful connection. This status bar is located in the
bottom right hand corner of the Cscape window.
In general, the Target number should match the Local number. The exception to this is when
the controller is being used as a "pass through" unit where other controllers on a CsCAN
network could be accessed through the local controller.
Determine connection status by examining feedback next to Local and Target in the status
bar of Cscape.
Table 23.1
–
Cscape Target & Local Numbers
Local: ###
If a number shows next to Local then communication is established to the local
controller.
Local: No Port
Cscape is unable to access the COM port of the PC. This could mean that Cscape is
configured for a COM port that is not present or that another program has control
of the COM port. Only one Cscape window can access a port at a time. Subsequent
instances of Cscape opened will indicate No Port.
Local: No Com
Cscape has accessed a PC COM port but is not communicating with the controller.
This typically occurs when the controller is not physically connected.
Local: ???
Unknown communication error. Close Cscape, power cycle the controller and
reopen Cscape with a blank project. Check Local.
Target: #(I, R, D)
If I (idle), R (run), or D (do I/O) shows next to Target number then communication is
established to the target controller.
Target: #(?)
Communication is not established to the target controller. Check node ID of
controller and set Target to match. Make sure local connection is established.