C
OMMISSIONING
44 / 157
System 6844(RC) - V03.00
hopf
Elektronik GmbH
Nottebohmstr. 41
• D-58511 Lüdenscheid • Tel.: +49 (0)2351 9386-86 • Fax: +49 (0)2351 9386-93 • Internet: http://www.hopf.com • E-Mail: [email protected]
4.4.3 Keypad Inputs / Main Menu Activation
The main menu is activated by pressing the
ENT
key. The display changes from the
standard frame to the main menu:
Standard frame:
L O C
1 0 : 2 5 : 1 9
D - C
T U
0 1 / J U N / 2 0 1 0
M
Main menu:
S E T = 1
S H O W = 2
S . C L K = 3
I N I = 4
The required menu item is executed by entering the corresponding number.
An incorrect input number is either directly refused or checked for plausibility after
the
ENT
key is pressed. An
"INPUT ERROR"
message follows. The display then
returns to the standard frame.
All of the selection functions are not always required or used. The System functions
for which they are effective are indicated in the specification, at the beginning of
each sub-function. If such a function is called up by mistake this can be exited by
pressing the
BR
key.
4.5
Initialization
The base initialization of the equipment is carried out first. This enables the equipment to
synchronize with the Sync.-Source.
To initialize the System 6844(RC) GPS the menu items presented below are to be parame-
terized accordingly (see
Chapter 5.2 SET Menu - Basic Settings System 6844(RC)
). In do-
ing so attention should be paid to System and location specific requirements such as time
base, synchronization source and synchronization parameters.
Menu items required for the base parameterization:
MENU 1: #SET
1.01
TIME/DATE
1.02
DIF.-TIME
1.03
CHANGE_OVER DATE (Changeover Standard time / Summer time)
1.04
CHANGE_OVER DATE (Changeover Summer time / Standard time)
1.05
POSITION
MENÜ 2: #SHOW
2.31
SYSTEM-BYTE (Used Sync.-Source)
Shows the adjusted Sync.-Source.
All additional settings are to be carried out in accordance with the requirements and use of
the equipment.