3.1.6.1 Power Supply Unit Specifications
All DC power supply specifications are described in
Chapter 11 Technical Data
3.1.6.2 Fusing
Pay attention to the correct fusing of the power supply when connecting the System
6844(RC).
The corresponding performance data can be taken from the equipment nameplate. The Sys-
tem 6844(RC) is currently fitted with a power supply unit with a power consumption of max.
40VA.
If the internal fuse (device protection) trips it is highly probable that the
equipment is faulty. In this case the device should be checked in the facto-
ry.
3.1.7 Synchronization Source Connection
Depending on the version different synchronisation signals can be connected to the System
6844 (RC)
3.1.7.1 GPS Antenna Equipment
The GPS antenna equipment coaxial cable is connected to the BNC connector marked
"An-
tenna"
on the control board 6844(RC) of the System. More detailed specifications for the in-
stallation of the antenna equipment, such as cable lengths and types, can be found in the
manual "Antenna Equipment GPS".
3.1.7.2 Serial String
The synchronisation string is always connected to interface COM1. The correct signal level
has to be considered.
3.1.7.3 PPS (Pulse per second)
For PPS input an additional hardware depending on the signal level for
synchronisation is required.
Insofar this option is factory set the connection and the signal level are stat-
ed in the supplied manual.
3.1.7.4 DCF77 Pulse
For DCF77 pulse input an additional hardware depending on the signal
level for synchronisation is required.
Insofar this option is factory set the connection and the signal level are stat-
ed in the supplied manual.