VISTA-128BPT/VISTA-250BPT Installation and Setup Guide
6-10
Action Code
Action
Action Specifier
72
Access Point Exit by Partition
Partition #
73
Access Point Trigger On
Trigger #
74
Access Point Trigger Off
Trigger #
77
Access Point Group Enable
Group #
78
Access Point Group Disable
Group #
3. Enter the desired activation time
(when the action is to take place). Select from:
Activation
Time
Description
1
Beginning of time window.
2
End of time window.
3
During time window active period only (on at beginning of window, off at end).
For example, if bypass is selected to activate during the window, zones in a zone list are bypassed at the beginning of
the window and unbypassed at the end of the window.
4
Beginning and end of time window (e.g., a coffee break buzzer). In this example, if relay pulse is selected, the relay
pulses for 2 seconds at the beginning of the window, signaling the beginning of the coffee break. At the end of the
window it pulses again, signaling the end of coffee break.
5
Random time at the start of the time window (occurs within 30 minutes after the start of the time window).
NOTE:
Since the randomization for choice “5” occurs within 30 minutes after the start of the window, the time
window must be at least 30 minutes in duration.
6
Random time at the end of the time window (occurs within 30 minutes after the end of the time window).
7
Random during the time window (begins within 30 minutes after the start of the time window and ends within 30
minutes after the end of the time window).
NOTE:
Since the randomization for choice “7” occurs within 30 minutes after the start of the window, the time
window must be at least 30 minutes in duration.
Field
∗
04 must be enabled for randomization. A user must initiate a random schedule by entering one of the following
sequences:
•
[User Code]
+
[#]
+
[41]
. This will randomize, up to 30 minutes, the activation time of all devices, programmed for
randomization, assigned to the partition the sequence is entered in. Enter the sequence again to turn off the random
schedule.
•
[User Code]
+
[#]
+
[42]
. This is the same as the method above, except the randomization occurs only on devices
with activation times within 6 PM and 5 AM. Enter the same sequence again to turn off the random schedule.
UL
You must not program Random Scheduling of Time Driven Events for UL installations.
Time-Driven Events Programming
The following menu items must first be programmed in
Output Programming in the #93 Menu Mode
:
Enter Relay No.
(reference identification number)
Output Group
(if applicable)
Restriction
Output Type
(V-Plex or 4204)
Zone No.
(V-Plex)
ECP Address
(4204)
Relay No.
(4204)
Summary of Contents for VISTA-128BPT
Page 2: ......
Page 46: ......
Page 56: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide 4 10 ...
Page 88: ...V128BPT V250BPT Installation and Setup Guide 8 2 ...
Page 104: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide C 2 ...
Page 112: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide Glossary 6 ...
Page 118: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide Index 6 ...
Page 120: ...For the latest warranty information please go to www honeywell com security hsc resources wa ...
Page 121: ...NOTES ...
Page 122: ...NOTES ...
Page 123: ...NOTES ...