Section 3 – Installing the Control
3-9
Using 2-Wire Smoke Detectors on Zone 1
Zone 1 can support up to 16 2-wire smoke detectors.
The alarm current on zone 1 supports only one smoke detector in the alarmed state.
Compatible 2-Wire Smoke Detectors
DETECTOR TYPE
DEVICE MODEL #
Photoelectric, direct-wire
System Sensor 2W-B
Photoelectric w/heat sensor, direct-wire
System Sensor 2WT-B
Ionization w/B401B base
System Sensor 1451
Photoelectric duct detect (DH400 base)
System Sensor 2451
Ionization duct detector (DH400 base)
System Sensor 1451DH
Ionization, direct-wire
System Sensor 1100
Photoelectric w/B110LP base
System Sensor 2151
UL
These smoke detectors are UL Listed for use with the VISTA-128BPT/VISTA-250BPT and are the
only
2-wire
smoke detectors that may be used.
Wiring 2-Wire Smoke Detectors to Zone 1
2K EOL resistors must be used on fire zones and must be connected across the loop wires of each zone at the
last detector.
To wire 2-wire smoke detectors to zone 1, perform the following steps:
Step
Action
1
Select up to 16 2-wire smoke detectors from the list of compatible detectors.
2
Connect 2-wire smoke detectors across zone 1 terminals (10 and 11) as shown in
Figure 3-10
. Observe proper
polarity when connecting the detectors.
3
Connect the EOL resistor at the last detector in the loop across the zone 1 terminals.
The EOL resistor
must be connected across the loop wires at the last detector.
2k EOLR
ZONE 1
SMOKE
(+)
(-)
2-WIRE SMOKE
DETECTOR
10
11
(+)
(-)
Figure 3-10: 2-Wire Smoke Detector on Zone 1
Using 4-Wire Smoke Detectors on Zones 1 – 8
You may use as many 4-wire smoke detectors as can be powered from the panel's Auxiliary Power output without
exceeding the output's rating (750mA).
•
NFPA limits the number of 4-wire smoke detectors to 18 per zone.
•
Auxiliary power to 4-wire smoke detectors is not automatically reset after an alarm, and therefore must be
momentarily interrupted using either the J7 smoke detector reset output trigger or a 4204 Relay Module.
Compatible 4-Wire Smoke Detectors
Use any UL Listed 4-wire smoke detector that is rated for 10-14VDC operation and that has alarm reset time not
exceeding 6 seconds. Some compatible 4-wire smoke detectors are listed below.
Detector Type
Detector Model #
Photoelectric, direct wire
System Sensor 4W-B
Photoelectric w/heat sensor, direct wire
System Sensor 4WT-B
Summary of Contents for VISTA-128BPT
Page 2: ......
Page 46: ......
Page 56: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide 4 10 ...
Page 88: ...V128BPT V250BPT Installation and Setup Guide 8 2 ...
Page 104: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide C 2 ...
Page 112: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide Glossary 6 ...
Page 118: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide Index 6 ...
Page 120: ...For the latest warranty information please go to www honeywell com security hsc resources wa ...
Page 121: ...NOTES ...
Page 122: ...NOTES ...
Page 123: ...NOTES ...