Section 3 – Installing the Control
3-7
The minimum load on the alarm output must exceed 5mA at 12V for proper supervision operation.
UL
If a device such as a siren driver with a high-resistance trigger input (drawing less than 5mA) is used in a UL
Household Fire installation, the siren driver must independently supervise siren speaker wiring.
Using a Siren Driver
To install a siren driver, perform the following steps:
Step
Action
1
Mount the siren driver in the panel’s cabinet.
2
Wire the siren driver to the control and to the speaker(s). (See the driver’s instructions.)
3
Cut the blue jumper on the upper left-hand corner of the panel’s PC board.
4
Program Zone 970 with no response type (00).
Disabling the Supervision of the Alarm Output
To install the alarm output and disable the supervision feature, perform the following steps:
Step
Action
1
Wire the devices to terminals 4 and 5, observing polarity if necessary.
2
Cut the blue jumper on the upper left-hand corner of the panel’s PC board.
3
Program Zone 970 with no response type (00).
Telephone Line Connections
Connect the main dialer output to telephone company lines using the cable supplied.
UL
The telephone line inputs have overvoltage protection in accordance with UL1459, as specified in UL985/UL1023.
The system is shipped defaulted for Contact ID format. It is the only format capable of uniquely reporting all 250
zones, as well as openings and closings for all 250 users. This requires central stations to be equipped with the
Honeywell MX8000 receiver or equivalent. If you need an update, contact your distributor.
To prevent the risk of shock, disconnect phone lines at the telco jack before servicing.
If the communicator is connected to a PABX, be sure it has a backup power supply that can support the PABX for 24
hours (central station) or 60 hours (remote station). Many PABXs are
not
power-backed up, and this can result in a
communication failure if power is lost
.
Reporting Formats
The system supports the following formats:
ADEMCO Contact ID; ADEMCO 10-Digit Contact ID and 4 + 2 Express.
Summary of Contents for VISTA-128BPT
Page 2: ......
Page 46: ......
Page 56: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide 4 10 ...
Page 88: ...V128BPT V250BPT Installation and Setup Guide 8 2 ...
Page 104: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide C 2 ...
Page 112: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide Glossary 6 ...
Page 118: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide Index 6 ...
Page 120: ...For the latest warranty information please go to www honeywell com security hsc resources wa ...
Page 121: ...NOTES ...
Page 122: ...NOTES ...
Page 123: ...NOTES ...