VISTA-128BPT/VISTA-250BPT Installation and Setup Guide
3-18
To install the relay modules, see
Figure 3-19 and
perform the following steps:
Step
Action
1
Set the 4204 DIP switches for a device address
01-15
.
Do not use an address being used by another device (keypads, RF receivers, etc.).
2
Mount the 4204 Module per the instructions provided with them.
3
Connect the module’s wire harness to the control (6, 7, 8, and 9). Plug the connector (other end of harness) to
the module.
If you are mounting remotely, homerun each module to the control. The table below shows the maximum wire
run lengths.
Wire Gauge
Maximum Length
#22
125 feet
#20
200 feet
#18
300 feet
#16
500 feet
4204 ADDRESS SETTINGS
("—" means "OFF")
DETERMINE 4204'S ADDRESS: CONTROL'S INSTRUCTIONS SPECIFY ADDRESS
TO USE. "0" ADDRESS SETTING SHOWN (AS SHIPPED).
SWITCH
NUMBER
0
1
2
3
4
5
6
7
8
9
10
11 12 13
14 15
2
ON — ON — ON — ON — ON — ON — ON — ON —
3
ON ON — — ON ON — — ON ON — — ON ON — —
4
ON ON ON ON — — — — ON ON ON ON — —
— —
5
ON ON ON ON ON ON ON ON — —
— — — — — —
1
2
3
4
5
Þ
OFF
ON
DIP SWITCH
(WHITE AREAS DENOTE SWITCH HANDLES)
POSITIONS 2-6:
POSITION 1:
ENABLES/DISABLES COVER TAMPER.
ON
= TAMPER DISABLED,
OFF
= TAMPER ENABLED. SHOWN DISABLED AS SHIPPED.
6
ON ON ON ON ON ON ON ON
6
7
16
17 18
19
20
21
22
23 24
25
26
27 28 29
30 31
ON — ON — ON — ON — ON — ON — ON — ON —
ON ON — — ON ON — — ON ON — — ON ON — —
ON ON ON ON — — — — ON ON ON ON — — — —
ON ON ON ON ON ON ON ON — — — — — — — —
— — — — — — — —
— — — — — — —
—
ON ON ON ON ON ON ON ON
POSITION 7:
NO FUNCTION
TB2
12
11
10
9
8
7
6
5
4
3
2
1
(–) GROUND
(+) 12V
YEL
BLK
GRN
RED
13
14
15
16
DIP SWITCH
FOR SETTING DEVICE ADDRESS
AND ENABLING/DISABLING TAMPER
COVER TAMPER
(REED)
SWITCH
TB1
4204
4-PIN TOUCHPAD PLUG
3
2
RELAY
1
4
RELAY CONTACTS ARE
NOT SUPERVISED
TYPICAL
(SHOWN "OFF")
C
NC
NO
C
NC
NO
C
4204-005-V0
NC
NO
C
NC
NO
EITHER OR BOTH
CAN BE USED
DATA IN
FROM CONTROL
DATA OUT
TO CONTROL
RELAY
RELAY
RELAY
4204 CONNECTIONS
DIP SWITCH SETTINGS
1
2
3
4
5
6
7
Figure 3-19: 4204 Relay Module
Installing 4101SN Relay Modules
The 4101SN V-Plex Single Output Relay Module is a serial number polling loop output device. The 4101SN features the
following:
•
Form C relay contacts rated at 2A, 28VAC/VDC with contact supervision.
The position of the relay is supervised, but not the actual external contact wiring.
•
One class B/style B EOLR-supervised auxiliary input zone.
•
Operating power and communication with control panels via the V-Plex polling loop.
•
Electronics mounted in a small plastic case with tamper-protected cover.
Connect the device to the polling loop, terminals 24 (+) and 25 (-). Be sure to observe polarity.
Summary of Contents for VISTA-128BPT
Page 2: ......
Page 46: ......
Page 56: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide 4 10 ...
Page 88: ...V128BPT V250BPT Installation and Setup Guide 8 2 ...
Page 104: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide C 2 ...
Page 112: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide Glossary 6 ...
Page 118: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide Index 6 ...
Page 120: ...For the latest warranty information please go to www honeywell com security hsc resources wa ...
Page 121: ...NOTES ...
Page 122: ...NOTES ...
Page 123: ...NOTES ...