VISIONPRO
®
8000 WITH REDLINK™
68-0312—03
46
610
Water Leak Alert
is [See Settings]
Normally Open
Normally Closed
Normally Open Both
Yes
Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed:
Normally Open: The Dry Contact device is
normally open and will close when the device
detects water.
Normally Closed: The Dry Contact device is
normally closed and will open when the device
detects water.
611
Shutdown Alert
None
S1
S2
S3
S4
None
Both
Yes
Dry Contact Alerts require an Equipment
Interface Module.
Select the terminals wired to the System
Shutdown Dry Contact Device.
612
Shutdown Alert is
[See Settings]
Normally Open
Normally Closed
Normally Open Both
Yes
Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed:
Normally Open: The Dry Contact device is
normally open and will close when the device
detects a problem.
Normally Closed: The Dry Contact device is
normally closed and will open when the device
detects a problem.
613
Service Alert
None
S1
S2
S3
S4
None
Both
Yes
Dry Contact Alerts require an Equipment
Interface Module.
Select the terminals wired to the Service
Needed Dry Contact Device.
614
Service Alert is
[See Settings]
Normally Open
Normally Closed
Normally Open Both
Yes
Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed:
Normally Open: The Dry Contact device is
normally open and will close when the device
detects a problem.
Normally Closed: The Dry Contact device is
normally closed and will open when the device
detects a problem.
615
Fan Failure Alert
None
S1
S2
S3
S4
None
Both
Yes
Dry Contact Alerts require an Equipment
Interface Module.
Select the terminals wired to the Fan Failure
Dry Contact Device.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Requires
EIM
Notes