
VISIONPRO
®
8000 WITH REDLINK™
39
68-0312—03
408
Max. Cool
Recovery Ramp
Rate
Off
1° F/hr to 20° F/hr
6° F/hr
Commercial No
Off: The cooling system will begin recovery at
the time that is scheduled.
When a
Maximum Recovery Ramp Rate
is
set, the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a
Maximum Recovery Ramp Rate
based
on the rate that the cooling system can
recover at for a mild day in your region.
Default setting is 6° F / hour.
Set an
Outdoor Temperature
that is
representative of a mild day in your region to
be associated with the
Maximum Recovery
Ramp Rate
.
The thermostat will begin recovery at the
optimal time based on a calculated ramp rate,
allowing the system to recover on time and
save energy during changing outdoor
conditions.
During recovery, the setpoint changes at a
rate in degrees per hour depending on the
outdoor temperature.
408
Max. Cool
Recovery Outdoor
Temp
Off
-20° F to 100°F
70° F
Commercial No
Off:
The cooling system will begin recovery at
the time that is scheduled.
When a
Maximum Recovery Ramp Rate
is
set, the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a
Maximum Recovery Ramp Rate
based
on the rate that the cooling system can
recover at for a mild day in your region.
Default setting is 6° F / hour.
Set an
Outdoor Temperature
that is
representative of a mild day in your region to
be associated with the
Maximum Recovery
Ramp Rate
.
The thermostat will begin recovery at the
optimal time based on a calculated ramp rate,
allowing the system to recover on time and
save energy during changing outdoor
conditions.
During recovery, the setpoint changes at a
rate in degrees per hour depending on the
outdoor temperature.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Requires
EIM
Notes