background image

VISIONPRO

®

 8000 WITH REDLINK™

127

68-0312—03

Fig. 325. Hot water radiant heat with backup forced air 

heat. Zoned with forced air zone panel and hot water 

panel.

Fig. 326. Hot water fan coil with forced air furnace backup 

heat.

M31485

HOT WATER 

RELAY PANEL

RH

W

W

W2

W3

W

Y

G

R

C

HZ311, HZ322, OR HZ432 ZONE PANELS COULD BE USED TO 

CONTROL A FORCED AIR FURNACE ZONED WITH DAMPERS.

AN AQ2000 SERIES HOT WATER ZONE PANEL OR OTHER 

RELAY-BASED HOT WATER ZONE 3 PANEL COULD BE USED.

L

TO THERMOSTAT

THERMOSTAT/EIM

CONV

ZONE 1

ZONE 1

1

2

1

2

RELAY

3

1

W

W2

W3

W

Y

G

R

C

CONFIGURE THE THERMOSTAT TO ENERGIZE THE FAN 

WITH A CALL FOR HEAT.

THE BOILER IS CONTROLLING THE CIRCULATOR PUMP 

IN THIS DIAGRAM.

L

TO THERMOSTAT

THERMOSTAT/EIM

CONV

FURNACE

M31486

1

2

2

1

BOILER

T

T

RELAY

3

1

Summary of Contents for TH8320R1003

Page 1: ...ensors or Dry Contact Devices Dry Contact Devices can be used to trip pre set or customized alerts on the thermostat home screen Note Dry Contact Alerts require an Equipment Interface Module EIM User Interaction Log The interaction log stores history of thermostat setting changes including temperature system and installer setup You can use the interaction log to save time by determining if the iss...

Page 2: ...4 Linking RedLINK Accessories 14 Mounting Optional Accessories 58 Data Logs 73 Alerts Log 73 User Interactions Log 73 Dry Contact Alerts 74 Setting the Time Date 61 Setting the Fan 61 Setting System Mode 61 Installer Tests 57 Using the Equipment Test 57 Using the Wireless Signal Strength Test 58 Indoor Air Quality IAQ Control 80 Humidification 80 Set up Humidification 80 Control Humidification Lev...

Page 3: ...dLINK displays Aux Heat On when the thermostat turns the auxiliary heat on Interstage Differential Comfort The thermostat keeps the indoor temperature within 1 degree of the setpoint droop less control The thermostat turns on stage 2 when the capacity on stage 1 reaches 90 When the interstage differential is set to 1 0 or higher the ther mostat stages the equipment based on how far the indoor temp...

Page 4: ...x 4 7 8 x 2 1 2 152 x 124 x 64 Black Portable Comfort Control REM5000R1001 32 to 120 F 0 to 48 9 C 5 to 90 Non Condensing 20 to 120 F 28 9 to 48 9 C 6 1 4 x 3 1 8 x 1 5 8 158 x 80 x 38 Arctic White Gray Wireless Entry Exit Remote REM1000R1003 32 to 120 F 0 to 48 9 C 5 to 90 Non Condensing 20 to 120 F 28 9 to 48 9 C 3 15 16 x 1 15 16 x 5 8 101 x 50 x 16 Arctic White Wireless Vent and Filter Boost R...

Page 5: ...70 x 8 Brushed Stainless Steel Discharge or Return Air Sensor 10K ohm Negative Temperature Coefficient C7735A1000 0 to 200 F 17 8 to 93 3 C 20 to 120 F 28 9 to 48 9 C Probe 3 3 4 x 1 4 77 x 6 4 Cap Diameter 2 7 16 62 Gray Discharge or Return Air Sensor 20K ohm Negative Temperature Coefficient C7041 4 3 16 x 2 5 16 x 1 11 16 107 x 59 x 43 Discharge or Return Air Sensor 20K ohm Negative Temperature ...

Page 6: ...ller Test Reset Thermostat to Factory Default Settings The password date code is located on the back of the thermostat see Fig 4 Fig 4 Finding thermostat password You can also find the password date code by pressing MENU selecting Dealer Information and then scrolling down to see the Date Code Residential Résidentiel 1 800 468 1502 http yourhome honeywell com Commercial Commerciale 1 888 245 1051 ...

Page 7: ...has been setup WITHOUT an Equipment Interface Module or the TrueZONE Wireless Adapter and you would like to add one you must reset the thermostat back to factory defaults Press MENU Installer Options scroll down to select Reset to Defaults Model Numbering TH8321 TH8320 TH8110 Stages 3H 2C HP 2H 2C CONV 3H 2C HP 2H 2C CONV 1H 1C HP 1H 1C CONV Residential or Commercial Dual Powered C Wire or Battery...

Page 8: ... to Selecting Thermostat Location beginning on page 11 NOTE If an EIM is mounted inside a metal cabinet such as a commercial rooftop unit it is recommended to use a THM4000R1000 Wireless Adapter for extended wireless range Mount the Wireless Adapter outside the metal cabinet and connect to the ABCD terminals at the EIM The Wireless Adapter functions as a remote antenna for the EIM After it is wire...

Page 9: ...ypass Humidifier is installed mount the Discharge Air Temperature Sensor downstream of the Bypass Humidifier See Fig 11 12 Selecting Return Air Temperature Sensor Mounting Location 1 Install the Return Air Temperature Sensor on the return duct in a location where the air is mixed well Mount the Return Air Temperature Sensor downstream of a Bypass Humidifier Dehumidifier or Ventilator See Fig 8 12 ...

Page 10: ...als at the EIM 4 Setup the S1 S2 S3 or S4 terminals in the Installer Setup at the thermostat Fig 13 Mounting Discharge Return Air Sensor MOUNT RETURN SENSOR HERE MOUNT DOWNSTREAM OF BYPASS HUMIDIFIER DEHUMIDIFIER OR VENTILATOR HEAT EXCHANGER BLOWER VENTILATOR OR DEHUMIDIFIER MOUNT DISCHARGE SENSOR HERE MOUNT DOWNSTREAM OF BYPASS HUMIDIFIER BYPASS HUMIDIFIER M33078A MOUNT RETURN SENSOR HERE MOUNT D...

Page 11: ...ng box 1 Press button on top and pull to remove the wallplate Fig 15 Separate wallplate from thermostat 2 Position and level the wallplate for appearance only 3 Use a pencil to mark the mounting holes 4 Remove the wallplate from the wall and if drywall drill two 3 16 in holes in the wall as marked For firmer material such as plaster drill two 7 32 in holes Gently tap anchors provided into the dril...

Page 12: ...batteries Refer to Fig 20 NOTE The relay outputs and inputs on the thermostat do not function when used with an Equipment Interface Module or TrueZONE Wireless Adapter Fig 20 Inserting wires in thermostat terminal block Remove Coin Cell Battery Tab 1 Remove tab to activate coin cell battery NOTE Coin cell battery saves time and date during a power loss Fig 21 Remove coin cell battery tab Mounting ...

Page 13: ... Wire and power TrueSTEAM 2 Connect the ABCD terminals between TrueSTEAM and the THM4000 Wireless Adapter 3 Adjust the DIP Switches on TrueSTEAM as follows when using the Wireless Adapter DIP3 UP DIP4 UP DIP5 DOWN Fig 27 Powering TrueSTEAM wireless adapter Entry Exit Remote or Vent Boost Remote 1 Remove the cover 2 Insert the CR2450 coin cell battery included into the slot at the bottom of the rem...

Page 14: ...lease the CONNECT button on the EIM Make sure the Connected light is flashing green Fig 31 EIM CONNECT button NOTE If the Connected light does NOT flash green another system may be in the listening mode Please exit the listening mode at the other sys tem and then try again Green Flashing In Listening Mode system is ready to add RedLINK devices Green Steady RedLINK devices are communi cating Red Re...

Page 15: ...ng mode If it detects no activity for 15 minutes it exits listening mode Completing Initial Setup 5 Finish the setup by selecting the desired options Touch Done after you select the last option you want to change Fig 37 Thermostat type The thermostat now displays its Home screen and the thermostat setup is complete Fig 38 Thermostat home screen Adding RedLINK Accessories to the Thermostat If you w...

Page 16: ...ermostat after all new RedLINK accessories are connected Fig 44 NOTE Thermostat displays a count down timer while in the listening mode If it detects no activity for 15 minutes it exits listening mode Locating the Connect Buttons on RedLINK Accessories Wireless Outdoor Sensor 1 Press and quickly release the CONNECT button on the Wireless Outdoor Sensor After a short delay up to 15 seconds the ther...

Page 17: ...nutes To begin again press and hold in the lower right corner of the screen until the display changes about 3 seconds See Fig 48 Fig 48 Restarting the linking process RedLINK Internet Gateway 1 Press and quickly release the button on the bottom of the Internet Gateway After a short delay the RedLINK sta tus light will glow steady green Fig 49 RedLINK Internet Gateway connect button NOTE The Intern...

Page 18: ...3 Fig 53 4 Select the Indoor Sensor name from the list and press Done The Indoor Sensor names are used when select ing which sensor to use for temperature control humidifi cation control and dehumidification control Fig 54 NOTE If you link more than 1 wireless indoor sensor and forget to name them you will be prompted to name each wireless indoor sensor after you exit wireless setup See Fig 55 Fig...

Page 19: ...available when you access Installer Options For more information on each press Help on the thermostat or see Table 1 Fig 60 MCR34022 Dealer Information Installer Options MCR33975 TH8321R1001 Date Code 1324 Residential Résidentiel 1 800 468 1502 http yourhome honeywell com Commercial Commerciale 1 888 245 1051 http customer honeywell com Honeywell Golden Valley MN 55422 RoHs Compliant Conformité Ro...

Page 20: ... LOGS to turn off on the Alerts Log or Interaction Log Wireless Manager Select WIRELESS MANAGER to add remove rename or view the connected wireless accessories Reset To Defaults Select RESET TO DEFAULTS to place all thermostat settings back to the factory settings Note If the thermostat has been setup WITHOUT an Equipment Interface Module or the TrueZONE Wireless Adapter and you would like to add ...

Page 21: ...U is not displayed when ISU 200 Heating System is set to Conv Forced Air Radiant Heat Other or None Cool Only See Geothermal Radiant Heat beginning on page 78 203 Radiant Stage 1 None U1 U2 U3 Default varies based on previous selections Both No This ISU is only displayed when ISU 201 Heating Equipment is Geothermal Radiant Geothermal Radiant Heat must be wired to a universal terminal U1 U2 or U3 U...

Page 22: ...cial Both No Conventional Cool Stage 3 and 4 are only available if ISU 101 is Commercial Cool Stage 3 and 4 must be wired to a universal terminal U1 U2 or U3 Heat Pumps Maximum of 2 Compressor Stages for heat pump systems 202 207 Heat Stages Backup Heat Stages 1 3 Default is 1 stage if ISU 101Application is Residential Default is 2 stages if ISU 101Application is Commercial Both No Maximum of 3 He...

Page 23: ...ed when ISU 201 Heating Equipment is Other 212 Backup Heat Type None Electric Gas Oil None Both No This ISU is only displayed when ISU 201 Heating Equipment is Radiant Heat or Other When ISU 201 Heating Equipment is Radiant Heat the thermostat keeps the Radiant Heat on when it calls for Backup Heat When ISU 201 Heating Equipment is Other you can select how the backup operates See ISU 215 213 Backu...

Page 24: ...evious selections Both No TH8321 Thermostat Only This ISU is only displayed on the TH8321 thermostat when it is wired directly to the equipment Equipment Interface Module is NOT used The thermostat can support up to 2 backup heat stages for heat pump applications When there are 2 backup heat stages backup heat stage 2 must be wired to U1 U1 is a normally open dry contact when configured for a stag...

Page 25: ...izer and Time of Day TOD Operation beginning on page 106 Notes The economizer module determines when outdoor conditions are favorable for free cooling Heat Pump Fault When 24 volts is detected on the L A terminal compressor monitor the thermostat displays a message to alert the user when the heat pump requires service The L A terminal sends a continuous output to a zone panel when the thermostat i...

Page 26: ...which include Backup Heat Droop Backup Heat Upstage Timer Outdoor Temperature Lockouts and Cycle Rate settings per stage Note Outdoor Temperature Lockouts only apply to Heat Pump applications Advanced Options The Installer Setup displays both Basic and Advanced Options Advanced temperature control options include Finish With High Cool Stage Finish With High Heat Stage and Temperature Differential ...

Page 27: ...ust rise to the selected differential setting before the thermostat turns on the stage of cooling For example if stage 3 is set to 2 F 1 0 C the indoor temperature must be 2 F 1 0 C away from the setpoint before stage 3 turns on When set to Comfort the thermostat uses the stage of cooling as needed to keep the indoor temperature within 1 F 0 5 C degree of the setpoint 303 Cool Differential Stage 4...

Page 28: ... temperature must drop to the selected differential setting before the thermostat will turn on the stage of heating For example if stage 2 is set to 2 F 1 0 C the indoor temperature must be 2 F 1 0 C away from the setpoint before stage 2 turns on When set to Comfort the thermostat will use the stage of heating as needed to keep the indoor temperature within 1 F 0 5 C degree of the setpoint 305 Hea...

Page 29: ...or adjust this ISU This ISU is only displayed if ISU 201 Heating Equipment is Air to Air Heat Pump Geothermal or Geothermal Radiant and there are 2 compressor stages The indoor temperature must drop to the selected differential setting before the thermostat will turn on the stage of heating For example if stage 2 is set to 2 F 1 0 C the indoor temperature must be 2 F 1 0 C away from the setpoint b...

Page 30: ...nly displayed when Backup Heat Droop Stage 1 is set to 2 F or higher ISU 308 309 312 Outdoor Lockout Heat Pump Off 5 F to 60 F in 5 F increments Off See Notes Both No ISU 312 Heat Pump Outdoor Lockout requires an outdoor sensor Default is 40 F if ISU 201 Heating Equipment is Air to Air Heat Pump and ISU 218 Backup Heat Type is Gas Oil Default is Off if ISU 201 Heating Equipment is Air to Air Heat ...

Page 31: ...will cycle is 3 times per hour 10 minutes on 10 minutes off The system cycles less often when load conditions are less than or greater than a 50 load 314 Cool Compressor Cycles Per Hour Stage 1 Note Stage 1 is not displayed if there is only 1 stage 1 to 6 CPH 3 Both No This ISU is only displayed when ISU 207 Cool Compressor Stages is set to 1 stage Cycle rate limits the maximum number of times the...

Page 32: ...when load conditions are less than or greater than a 50 load 315 Heat Cycles Per Hour Stage 1 Note Depending on the application the text displayed on the screen may show the specific heatingequipment type Stage 1 is not displayed if there is only 1 stage 1 to 12 CPH Conv Forced Air 5 CPH Heat Pump 3 CPH Radiant Heat 3 CPH Both No This ISU is only displayed when ISU 207 Heat Stages is set to 1 stag...

Page 33: ...ermal Radiant Heat 3 CPH Steam 1 CPH Gravity 1 CPH 315 Heat Cycles Per Hour Stage 3 Note Depending on the application the text displayed on the screen may show the specific heatingequipment type 1 to 12 CPH Conv Forced Air 5 CPH Heat Pump 3 CPH Radiant Heat 3 CPH Both No This ISU is only displayed when ISU 207 Heat Stages is set to 3 stages Cycle rate limits the maximum number of times the system ...

Page 34: ... times per hour 10 minutes on 10 minutes off The system cycles less often when load conditions are less than or greater than a 50 load The recommended cycle rate settings are below for each heating equipment type Standard Efficiency Gas Forced Air 5 CPH High Efficiency Gas Forced Air 3 CPH Oil Forced Air 5 CPH Electric Forced Air 9 CPH Hot Water Fan Coil 3 CPH Hot Water Radiant Heat 3 CPH Geotherm...

Page 35: ...uches the message center area on the thermostat Note The message center displays Press HERE to Start Occupancy The system will then maintain a comfortable temperature until the occupied period ends This option is recommended for cost savings when the workplace is used infrequently or arrival times change from day to day example schools After the user touches Press HERE to Start Occupancy the user ...

Page 36: ...utdoor sensor the Minimum Recovery Ramp Rate is used 405 Min Heat Recovery Outdoor Temp Off 20 F to 100 F 0 F Commercial No Off The heating system will begin recovery at the time that is scheduled When a Minimum Recovery Ramp Rate is set the thermostat will begin recovery early to ensure the temperature is reached at the scheduled time Set a Minimum Recovery Ramp Rate based on the rate that the he...

Page 37: ...grees per hour depending on the outdoor temperature 406 Max Heat Recovery Outdoor Temp Off 20 F to 100 F 40 F Commercial No Off The heating system will begin recovery at the time that is scheduled When a Maximum Recovery Ramp Rate is set the thermostat will begin recovery early to ensure the temperature is reached at the scheduled time Set a Maximum Recovery Ramp Rate based on the rate that the he...

Page 38: ...tdoor sensor the Minimum Recovery Ramp Rate is used 407 Min Cool Recovery Outdoor Temp Off 20 F to 100 F 90 F Commercial No Off The cooling system will begin recovery at the time that is scheduled When a Minimum Recovery Ramp Rate is set the thermostat will begin recovery early to ensure the temperature is reached at the scheduled time Set a Minimum Recovery Ramp Rate based on the rate that the co...

Page 39: ...grees per hour depending on the outdoor temperature 408 Max Cool Recovery Outdoor Temp Off 20 F to 100 F 70 F Commercial No Off The cooling system will begin recovery at the time that is scheduled When a Maximum Recovery Ramp Rate is set the thermostat will begin recovery early to ensure the temperature is reached at the scheduled time Set a Maximum Recovery Ramp Rate based on the rate that the co...

Page 40: ... user presses Home Occupied at the Entry Exit Remote Select None to delete this temperature setting The thermostat only responds to the Entry Exit Remote if a temperature is pre set at this screen See Wireless Entry Exit Remote beginning on page 110 412 Residential Entry Exit Remote Home Heat Setpoint Commercial Entry Exit Remote Occupied Heat Setpoint None 40 F to 90 F Note setpoint is limited ba...

Page 41: ...ect None to delete this temperature setting The thermostat only responds to the Entry Exit Remote if a temperature is pre set at this screen See Wireless Entry Exit Remote beginning on page 110 500 Wired Sensor on S Terminals No Yes No Both No This ISU is only displayed if an S1 S4 terminal is available 500 Wired Remote Indoor Sensor No Yes No Both No The thermostat will not display the Wired Remo...

Page 42: ...nsor Name in Temp Avg Yes or No Up to 6 Remote Indoor Sensors Sensors are Averaged T Stat Sensor and Remote Both No Select the sensors to be used for temperature control If you select more than one the thermostat will average the temperature readings from each sensor See Remote Indoor Sensors beginning on page 112 505 Outdoor Sensor None S1 S2 S3 S4 None Both No Select the terminals wired to the O...

Page 43: ...nal is available 600 Full Drain Pan Dry Contact Alert No Yes No Both Yes Dry Contact Alerts require an Equipment Interface Module This ISU is only displayed if an S1 S4 terminal is available See Dry Contact Alerts beginning on page 74 600 Dirty Filter Dry Contact Alert No Yes No Both Yes Dry Contact Alerts require an Equipment Interface Module This ISU is only displayed if an S1 S4 terminal is ava...

Page 44: ...e is closed when the room is occupied and will open when the room is unoccupied 603 Remote Setback Time Delay 0 to 30 minutes in 5 minute increments 0 minutes Commercial Yes Remote Setback requires an EIM Equipment Interface Module The Remote Setback Time Delay forces the thermostat to wait before it switches from Occupied to the Remote Setback temperature settings When set to 0 minutes the thermo...

Page 45: ...he type of device installed Normally Open The Dry Contact device is normally open and will close when the device detects the drain pan is full Normally Closed The Dry Contact device is normally closed and will open when the device detects the drain pan is full 607 Dirty Filter Alert None S1 S2 S3 S4 None Both Yes Dry Contact Alerts require an Equipment Interface Module Select the terminals wired t...

Page 46: ...is normally open and will close when the device detects a problem Normally Closed The Dry Contact device is normally closed and will open when the device detects a problem 613 Service Alert None S1 S2 S3 S4 None Both Yes Dry Contact Alerts require an Equipment Interface Module Select the terminals wired to the Service Needed Dry Contact Device 614 Service Alert is See Settings Normally Open Normal...

Page 47: ...or the type of device installed Normally Open The Dry Contact device is normally open and will close when the device detects a problem Normally Closed The Dry Contact device is normally closed and will open when the device detects a problem 619 Custom Alert Name View Edit Custom Alert View Edit Custom Alert Both Yes Dry Contact Alerts require an EIM Equipment Interface Module Enter a name for the ...

Page 48: ... Sensor for Hum T Stat Sensor Remote Indoor Sensor Name Remote Indoor Sensor Name Remote Indoor Sensor Name Remote Indoor Sensor Name Remote Indoor Sensor Name Remote Indoor Sensor Name Up to 6 Remote Indoor Sensors T Stat Sensor Both No Select a sensor to control humidification thermostat or an optional remote sensor If multiple sensors are installed you can use a different sensor for dehumidific...

Page 49: ...l Hum when Heat is On Hum when Fan is On Tstat Controls Fan Hum Controls Fan Defaults to Hum when Heat is On when ISU 800 Humidifier Type is Bypass or Fan Pwrd Defaults to Tstat Controls Fan when ISU 800 Humidifier Type is Steam Both No Hum when Heat is On The thermostat turns on the humidifier only if the heat is currently running and humidification is needed Hum when Fan is On The thermostat tur...

Page 50: ...he Humidification Sensor or the Dehumidification Sensor 904 Dehum Wiring None U1 U2 U3 Thermostat defaults to the next unused universal terminal U1 U2 U3 Both No Number of Universal Outputs TH8321 Thermostat U1 terminals Equipment Interface Module EIM U1 U2 and U3 terminals U1 U2 U3 are dry contacts that require power See Wiring IAQ Equipment or a Heat Cool Stage to the Universal Terminals beginni...

Page 51: ...nly displayed if ISU 908 Dehum Control is set to Cooling Droop The thermostat uses the cooling system to reduce humidity by lowering the temperature up to 5 F below the current cool setpoint until the desired humidity level is reached The thermostat keeps the temperature below the cooling setpoint until the desired humidity level is reached 912 User Dehumidifier in Heat Mode Use Dehumidifier in Co...

Page 52: ...ving space 920 Dehum Away Mode Low Limit Temp 70 F to 80 F 76 F Both No If the cooling system is used to control humidity while Dehumidification Away Mode is active the thermostat allows the cooling system to lower the indoor air to the Low Limit Temperature Setting to reach the dehumidification setting at ISU 920 920 Dehum Away mode Temp Setting 70 F to 99 F 85 F Both No The temperature maintaine...

Page 53: ...the ventilation equipment when ventilation is needed The fan is controlled by the equipment 1009 Number of Bedrooms 1 to 6 2 bedrooms Residential No This ISU is only displayed when ISU 1005 Ventilation Method is set to ASHRAE Residential only 1009 Size of House 1000 to 5000 sq ft in 100 sq ft increments 90 to 460 sq m 1000 sq feet Residential No This ISU is only displayed when ISU 1005 Ventilation...

Page 54: ...ion standard in a shorter run time Notes ISU 1014 Lockout Ventilation on Humidification or Dehumidification calls is not an option when you select ASHRAE is Priority The ability to lockout ventilation during the Sleep or Unoccupied program periods is not an option when you select ASHRAE is Priority 1013 Low Outdoor Temp Vent Lockout Off 20 F to 40 F in 5 F increments Off Both No Requires an outdoo...

Page 55: ...d in the system Some systems may have two UV devices one for the A Coil and another for Air Treatment A replacement reminder can be setup for each one Select 0 if no UV devices are installed 1105 UV Bulb 1 Reminder Note 1 is not displayed if there is only 1 UV Bulb Off 6 12 24 Calendar Months Off Both No UV Bulb 1 Replacement Reminder 1105 UV Bulb 2 Reminder Off 6 12 24 Calendar Months Off Both No...

Page 56: ...ight will be on continuous if the thermostat is powered with 24 VAC C wire or it will flash if the thermostat is powered with batteries only The light also turns on when the system setting is set to Em Heat Select On to use the light indicator or select Off to turn off the light 1500 Dealer Name Dealer Name None Both No Dealer information is displayed to the user when an alert is active and the us...

Page 57: ...ler Options and press SELECT 2 Enter the password date code when prompted See Finding Your Password Date Code to Access Installer Options beginning on page 19 for more information 3 Scroll down to Installer Test and press SELECT Fig 64 4 Select Equipment Test or Wireless Test Fig 65 CAUTION Equipment Damage Hazard Minimum compressor off time is bypassed during the Equipment Test Avoid cycling comp...

Page 58: ... mount the sensor in direct sunlight where hot or cold air blows on the sensor Discharge line from an outdoor compressor unit vent or fan causes inaccurate temperature readings where snow ice or debris can cover it MOUNTING C7089R1013 WIRELESS OUTDOOR SENSOR Use the following steps to mount the sensor see Fig 72 1 Mount the sensor on a vertical exterior wall at least 6 inches below any overhang Ch...

Page 59: ...ve the cover 2 Pull wires through wire hole 3 Position wallplate on wall level and mark screw hole positions with pencil 4 Drill holes at marked positions then tap in supplied wall anchors 5 Place wallplate over anchors insert and tighten mount ing screws see Fig 76 Fig 76 Mount wallplate to wall 6 Replace the cover on the remote sensor Entry Exit Remote or Vent Boost Remote Mounting the remote is...

Page 60: ... system mode heat cool outdoor temperature and humidity with optional outdoor sensor Current schedule Touch an arrow to change temperature setting and select a Temporary or Permanent Hold Indoor conditions Shows indoor temperature and humidity Current time Touch to set the current time date Alert Light On when alert message is active or system is set to EmHeat Flashes for battery only power on con...

Page 61: ... when heating or cooling system is on Circ Fan runs randomly about 35 of the time residential only Follow Schedule Fan controlled by program Fig 84 NOTE In commercial use touch Auto or On to temporar ily override the programmed fan schedule Setting System Mode 1 Touch SYSTEM to display system settings Fig 85 2 Touch desired option Heat Controls only the heating system Cool Controls only the coolin...

Page 62: ...or the Wake period 6 Touch other time periods Leave Return Sleep to set time and temperatures for each 7 Touch Done to save and exit Touch Cancel to exit with out saving changes Fig 91 NOTE Touch Cancel Period to eliminate any unwanted time period Touch Fan Setting to customize fan settings for any time period Table 3 Residential Use Default Schedule Period Start Time Heat Mon Fri Cool Mon Fri Hea...

Page 63: ...e a pre set occupied temperature if a person uses the room during an unoccupied period The new temperature will be maintained for 1 hour and can be adjusted up to the maximum time set by the installer Fig 94 The programmed schedule will resume when the override timer expires Touch Cancel Hold at any time to resume the program schedule Viewing Equipment Status 1 Touch MENU Fig 95 2 Select Equipment...

Page 64: ...want to schedule and touch Next for further scheduling details Custom Events lets you set up other days for special schedules US and Canadian Holiday options let you select from a list of holidays commonly observed in each country Fig 104 4 Make selections as prompted on each screen For more information see next two pages 5 Touch Done to save your settings Setting Custom Events Commercial Use This...

Page 65: ...ay Schedule menu 2 Select Add Edit Holidays A list of national holidays is displayed Fig 109 3 Touch the check box next to each holiday for which you want to maintain specific settings Touch or to scroll through the holiday list then touch Next Set the holiday schedule for Occupied or Unoccupied temperatures depending whether the building will be in use Fig 110 4 Touch or to select the Heat and Co...

Page 66: ...timer expires or the Occupied period ends NOTE This feature is available only when programmed by the installer Remote Setback Commercial Use During Occupied program periods an occupancy sensor directs the thermostat to go to REMOTE SETBACK settings when the room is empty If someone is in the room it uses the Occupied program period settings The thermostat ignores the occupancy sensor during Unoccu...

Page 67: ...ing to the next lowest number and check for frost condensation on your windows the next morning Con tinue to adjust the Window Protection setting to a lower number until frost condensation is no longer present NOTE Window Protection is available only if an outdoor air sensor is installed NOTE The thermostat controls humidification and dehu midification as needed to maintain the desired humidity le...

Page 68: ...e minimum on time to reduce humidity Run cooling and heating at the same time to reduce humidity without lowering the temperature Adjusting Ventilation Settings 1 Touch MENU and select Ventilation Fig 126 Fig 127 2 Select Mode Temporary Boost or Lockout then select appropriate options Fig 128 3 Touch Done to save your settings Touch Cancel to ignore changes Fig 129 Ventilation Options Mode Auto Ve...

Page 69: ... hour clock display Display Options Backlighting Continuous or On Demand Inactive Backlight Backlight level while the screen is not in use Requires C wire and Backlighting must be set to Continuous Screen Contrast Alert light options Scheduling options Adaptive recovery Default schedule Daylight saving time Fig 135 3 Touch Done to save your settings Touch Cancel to ignore changes Cleaning the Ther...

Page 70: ...g 141 Unlocked Full access allowed Partially locked Only temperature can be changed Fully locked No access allowed Fig 142 NOTE If you choose to use a password for additional security write it down for reference Viewing Dealer Information Check dealer information if you need to contact your installer for maintenance repairs or upgrades 1 Touch MENU Fig 143 2 Select Dealer Information Fig 144 3 Scr...

Page 71: ...tat keeps the compressor off for a few minutes before restarting to prevent equipment damage During this off time the message Wait is displayed on screen PRE OCCUPANCY PURGE COMMERCIAL USE ONLY This feature turns on the fan 1 to 3 hours before each occupied time period to provide a comfortable workplace when you arrive P I CONTROL A conventional mechanical or electronic thermostat does not control...

Page 72: ...r Setup Setup options are listed below See Thermostat Wiring Guides on page 129 and Equipment Interface Module wiring guides on page 130 Universal Output Options With Equipment Interface Module U1 U2 U3 Humidification ISU 803 Dehumidification ISU 904 Ventilation ISU 1002 Cool Stage 3 ISU 208 Cool Stage 4 ISU 209 Geothermal Radiant Heat ISU 203 204 TH8321 Thermostat Only U1 Humidification ISU 803 D...

Page 73: ...It can be turned on off and reset at the thermostat Fig 153 The Alerts Log contains information about the alert and system information The Alerts Log can include The alert name and description System details at the time of the alert The alert status snoozed dismissed recovered User Interactions Log The User Interactions Log can help a service technician save time by determining if the issue is rel...

Page 74: ...system for example smoke detection the thermostat will not call for heating cooling fan or IAQ equipment until the dry contact is deactivated or the feature is unconfigured at the thermostat Service Needed Alert When the dry contact device detects an issue that requires service the thermostat provides an alert to the user Fan Failure Alert The Fan Failure Alert protects the equipment when there is...

Page 75: ...lly closed it will open when the device detects water Refer to the instructions packed with the dry contact device to determine if it is normally open or normally closed Fig 160 6 If you are creating a custom alert type the alert name and press Done The alert name is what appears on the Home screen when the alert is detected See Fig 161 You can edit or confirm the alert name after you enter it Fig...

Page 76: ...ns on stage 2 when the capacity on stage 1 reaches 90 TO CHANGE DIFFERENTIAL SETTINGS 1 Select Advanced Options to view adjust differentials between all stages Fig 163 2 Default is Comfort Adjust differentials as needed Fig 164 Backup Heat Droop A Backup Heat Droop is available for any system with 2 heating types For example Heat Pumps with any type of Backup Heat Radiant Heat with any type of Bac...

Page 77: ...is not rising quickly enough to reach the setpoint in a reasonable time NOTE If the backup heat was used in the last 2 hours because the primary heat was not able to main tain the setpoint the thermostat may turn on the backup heat earlier when the user raises the set point This does NOT apply to heat pumps with fossil fuel backup heat TO CHANGE BACKUP HEAT DROOP SETTINGS 1 Select Basic Options or...

Page 78: ...mergency Heat and the Heat Pump is locked out Geothermal Radiant Heat The thermostat can be setup to control Geothermal Radiant Heat Geothermal Forced Air Heat and Backup Heat all from one thermostat The thermostat stages the equipment starting with the Geothermal Radiant Heat followed by Geothermal Forced Air Heat and then Backup Heat as needed to maintain the desired temperature The thermostat a...

Page 79: ...eothermal Radiant Heat and Geothermal Forced Air Heat are not used Set Up Geothermal Radiant Heat 1 Select Geothermal Radiant Heat as shown in Fig 169 Fig 169 2 Select the number of Radiant Heat Stages See Fig 170 Fig 170 3 Select the universal terminals wired to the Geothermal Radiant Heat See Fig 171 Fig 171 4 Select a Geothermal Forced Air Option For example if Geothermal Forced Air is used for...

Page 80: ... above a certain level To prevent frost or condensation the thermostat may turn off the humidifier before the humidity setting is reached To adjust the Window Protection setting press MENU scroll down and select Window Protection Window Protection is set on a scale from 1 10 A setting of 1 represents poorly insulated windows and a setting of 10 represents well insulated windows A lower number auto...

Page 81: ...w humidification if the last call was for heat Cool includes Cool and Auto If the system is in Auto mode the thermostat will allow humidifica tion if the last call was for cool A discharge sen sor is required to humidify in the Cool mode The thermostat prevents condensation in the duct work by not allowing the humidifier to run when the discharge temperature goes below the dew point temperature Th...

Page 82: ...emperatures poorly insulated windows require a lower Window Pro tection setting which will limit how much your humidifier can run 7 After you set the Window Protection setting check for frost condensation on your windows in the morning If frost condensation is present adjust the Window Protec tion setting to the next lowest number and check for frost condensation on your windows the next morning C...

Page 83: ...fication using the Cooling System When set for A C with Low Speed Fan or A C with High Speed Fan an overcooling limit can be set from 0 F to 3 F ISU 907 The thermostat uses the cooling system to reduce humidity by lowering the temperature up to 3 F below the current cool setpoint until the desired humidity level is reached If set for A C with Low Speed Fan configure U1 U2 or U3 as normally open or...

Page 84: ...tion requires a dedicated unit for dehumidification The thermostat can be set to control dehumidification in all modes Heat Off Cool ISU 912 Set up Dehumidification With Whole House Dehumidifier Some screens shown in this section may not appear on the thermostat depending on how you set up dehumidification 1 Select the Dehumidification Equipment in ISU 900 See Fig 194 Fig 194 2 If optional remote ...

Page 85: ... the fan when dehumidification is needed Equip Controls Fan Thermostat turns on the dehumidifier when dehumidification is needed The fan is controlled by the equipment Fig 199 7 Set the desired lockout option See Fig 200 Fig 200 NOTE ISU 1014 gives the option to lockout ventilation during calls for dehumidification This helps maintain the desired humidity level Dehumidification Away Mode Dehumidif...

Page 86: ...ion settings See Fig 205 Low Limit Temperature Setting If the cooling system is used to control humidity while Dehumidification Away Mode is active the thermostat allows the cooling system to lower the indoor air to the Low Limit Temperature Setting to reach the Dehumidification Setting at ISU 920 Temperature Setting The temperature maintained while Dehumidification Away Mode is active and the des...

Page 87: ... the thermostat will automatically enforce a 15 deadband between the humidification and dehumidification settings The thermostat will automatically switch between humidification and dehumidification to maintain the desired humidity level If humidification and dehumidification are setup to operate in the same system mode Heat Cool Off and you are sensing humidity from two different locations using ...

Page 88: ...set for A C with Low Speed Fan configure U1 U2 or U3 as normally open or normally closed ISU 905 and wire to the Low Speed Fan terminal on the equipment For example if the U1 U2 or U3 terminal is normally closed it will open when the thermostat calls for dehumidification See Wiring IAQ Equipment or a Heat Cool Stage to the Universal Terminals beginning on page 129 NOTE The thermostat will not lowe...

Page 89: ...this section may not appear on the thermostat depending on how you set up dehumidification 1 Select the Dehumidification Equipment in ISU 900 See Fig 216 Fig 216 2 If optional remote wireless indoor sensors are installed you can choose which sensor you want to use for dehu midification control For example you can use one sen sor for humidification control and another for dehumidification See Wirel...

Page 90: ...ication is needed Equip Controls Fan Thermostat turns on the dehumidifier when dehumidification is needed The fan is controlled by the equipment Fig 221 7 Set the desired lockout option See Fig 222 Fig 222 NOTE ISU 1014 gives the option to lockout ventilation on calls for dehumidification This helps main tain the desired humidity level Dehumidification Away Mode Dehumidification Away Mode for a co...

Page 91: ... etc ASHRAE 62 2 is not met during those times See ISU 1012 to select a Ventilation Priority Percent On Time The thermostat operates ventilation equipment based on a percentage entered in the installer setup ISU 1012 For example if Percent On Time is set to 50 the ventilation equipment will run at random times during a 1 hour period until it reaches a 50 run time approximately 30 minutes Default s...

Page 92: ... Humidification setting The thermostat must be in the heat mode to ventilate on high indoor humidity Set up Ventilation Some screens shown in this section may not appear on the thermostat depending on how you set up ventilation 1 Select the Ventilation Type in ISU 1000 See Fig 226 Fig 226 2 Select the terminals wired to the Ventilator or Fresh Air Damper See Fig 227 Fig 227 3 Select the Ventilatio...

Page 93: ...sidential or Unoccupied Commercial program periods Note This option is set by the user on the Ventila tion screen in the Menu d ASHRAE is Priority ASHRAE requires additional ventilation following a long off cycle The thermostat meets the ASHRAE 62 2 ventilation standard by run ning additional ventilation when outdoor conditions are favorable If ASHRAE cannot be met when out door conditions are fav...

Page 94: ...ig 235 When ISU 1012 Ventilation Priority is set to ASHRAE is Priority the screen below will indicate the maximum length of time that ventilation can be locked out over a 21 hour time period For example Ventilation Lockout Will Not Exceed 12 5 hours The length of time that ventila tion is locked out is limited to ensure that the ASHRAE 62 2 Ventilation Standard is met See Fig 236 Fig 236 10 Select...

Page 95: ...Boost or Lockout then select appropriate options Fig 241 3 Touch Done to save your settings Touch Cancel to ignore changes Fig 242 Ventilation Options Mode Auto Ventilation runs as programmed by the installer Off Ventilation remains off unless turned on using the timer On Ventilation is always on Fig 243 Temporary Boost Touch or to select how long to run ventilation temporarily To turn it off set ...

Page 96: ...NU then scroll to select Preferences 2 Press Reminders Fig 246 is displayed Fig 246 3 Select the reminder you want to set 4 Press or to set the timer length Ranges incre ments and units will change based on the reminder NOTE When set for run time days the thermostat tracks the amount of time the fan has run and compares that time against the number of run time days selected Fan run time is counted...

Page 97: ...ig 250 4 Press the up or down arrows to set the outdoor tempera ture and press Next Fig 251 NOTE A seasonal maintenance reminder will appear when the outdoor temperature reaches the level you select after a specified date 5 Press the up or down arrows to set the date to begin monitoring outdoor temperature The thermostat will not display a reminder unless the temperature you set is reached after t...

Page 98: ...essage Fig 256 10 To clear the Alert and turn off the Red Alert Light on the thermostat select Dismiss To create a new custom reminder 1 Touch Press HERE to edit at ISU 1200 see Fig 248 2 Press up or down arrows until Custom Reminder is dis played then press Next Fig 257 Fig 257 3 Touch Press HERE to edit to set the name of the reminder Fig 258 Fig 258 4 Use the arrows Delete and Space buttons to ...

Page 99: ...ustom Reminder should appear and press Next Fig 262 8 Select whether you want the reminder to appear only once or to be recurring and press Next Fig 263 9 If Recurring select how often you want the reminder to appear and press Next Fig 264 10 The preview of the custom reminder shows you what you ve selected You can load Custom Reminders to a microSD card to transfer from one thermostat to another ...

Page 100: ...puter go to http thermostatsetup honeywell com 2 Connect a microSD card to a USB adapter Then con nect the USB adapter to your computer Fig 268 3 Download the software upgrade file to the microSD USB adapter by clicking the indicated link on the web site 4 When the File Download box opens click Save 5 When the Save As box opens navigate to the directory of your USB device and save the file For exa...

Page 101: ...e ther mostat 8 See To Use the MicroSD Card in the Thermostat on page 101 To Use the MicroSD Card in the Thermostat 1 Slide card into the bottom of thermostat See Fig 269 2 Select the item to load or save Fig 270 3 Follow the prompts on the screen To add information from the card to the thermostat select Load from SD Card To put thermostat information on the card select Save to SD Card Fig 271 4 W...

Page 102: ...old time touch the Hold Until arrow buttons This time can be adjusted up to the maximum time set by the installer Fig 273 Touch Override to use a pre set occupied temperature if a person uses the room during an unoccupied period The new temperature will be maintained for 1 hour and can be adjusted up to the maximum time set by the installer Fig 274 The programmed schedule will resume when the over...

Page 103: ... settings length of event and frequency for the event Fig 280 4 Review the settings and touch Done to save them Touch Cancel to ignore the changes Fig 281 Setting Holiday Schedule Commercial Use This feature lets you customize temperature settings to be maintained on specified national holidays The thermostat resumes normal scheduling between selected holidays 1 Select US Holidays or Canadian Holi...

Page 104: ...NOTE The cool temperature can only be set higher than the unoccupied program setting and the heat tem perature can only be set lower than the unoccu pied program setting Initiating Occupancy Mode Commercial Use This feature keeps temperature at an energy saving level until you touch Press HERE to Start Occupancy When you arrive touch the message to maintain a comfortable temperature while the room...

Page 105: ...h are common in commercial applications Fig 289 Fig 290 Remote Setback Commercial Use The thermostat allows you to do REMOTE SETBACK when set up for commercial use This feature requires an occupancy sensor connected to the S1 S2 S3 or S4 terminals at the Equipment Interface Module During Occupied program periods an occupancy sensor directs the thermostat to go to REMOTE SETBACK settings when the r...

Page 106: ...mostat controls an economizer module to provide ventilation during occupied periods and free cooling when outdoor conditions are favorable In some climates the cooling system may run several hours when it may not be required to maintain indoor comfort When outdoor conditions are favorable ventilation with outdoor air can achieve the same level of comfort at lower cost Table 5 explains how the Econ...

Page 107: ...ay output connect to the A L A terminal at the thermostat or EIM and are set up at ISU 222 Fig 296 Pre Occupancy Purge The thermostat can be set up for Pre Occupancy Purge in the installer setup ISU 401 When setup for Pre Occupancy Purge the thermostat runs the fan 1 to 3 hours before each occupied period to provide a comfortable workplace upon arrival Options are Off and 1 to 3 hours Fig 297 Tabl...

Page 108: ...days before batteries are depleted The Portable Comfort Control will restore communication with the thermostat a few seconds after new batteries are installed Wireless Outdoor Sensor Replace batteries in your outdoor sensor when a warning appears on the thermostat screen about 60 days before batteries are depleted Fig 300 To replace the batteries 1 Remove the sensor from the bracket 2 Detach cover...

Page 109: ...ill be depleted within 2 3 weeks During normal operation the status light remains off Fig 301 To replace the batteries 1 Remove the sensor from wallplate 2 Install 2 fresh AAA alkaline batteries If the status light flashes green batteries are good if it flashes red you must use fresh batteries 3 Attach sensor to wallplate The sensor will restore communication with the thermostat a few seconds afte...

Page 110: ...ensors REDLINK INTERNET GATEWAY The Honeywell RedLINK Internet Gateway gives you remote access to your VisionPRO thermostat from the web smart phone or tablet You can view or adjust indoor temperature system mode and other settings The Gateway can also send alerts to as many as 6 email addresses to notify you if a problem occurs WIRELESS ENTRY EXIT REMOTE This device mounts beside your door for on...

Page 111: ... Reading temperature at the Portable Comfort Control If the thermostat is being averaged with remote indoor sensors and you select THERMOSTAT on the Portable Comfort Control you will see the temperature average from the remote indoor sensors and the thermostat NOTE If the thermostat is not part of the temperature average then you will only see the temperature average from the remote indoor sensors...

Page 112: ...ors are installed you can choose which sensor you want to use for humidification control You can use a different sensor for dehumidification When using multiple remote indoor sensors you should name each sensor after you link them to the thermostat See Wireless Indoor Sensor beginning on page 18 for more information Naming the sensors allows you to select the appropriate sensor for Humidification ...

Page 113: ... to the thermostat If you connect a Wired Indoor Sensor network to the S1 S2 S3 or S4 terminals you can connect up to 5 Wireless Indoor Sensors to the thermostat The indoor air sensor has a 1 year battery life Battery level indicators when batteries are inserted Good Status light flashes green for 5 seconds Low Status light flashes red for 5 seconds Use fresh batteries Battery level indicators dur...

Page 114: ...that is being used for control In Fig 309 the humidity reading is from the remote indoor sensor Fig 309 If you are sensing Humidity from two separate locations one for humidification and another for dehumidification you can select which humidity reading to display on the home screen In Fig 310 the humidity reading is from the Main Level remote indoor sensor based on the setting in ISU Fig 310 ...

Page 115: ...9 8659 14 10 0 42506 86 30 0 8315 16 8 9 40394 88 31 1 7986 18 7 8 38400 90 32 2 7672 20 6 7 36519 92 33 3 7372 22 5 6 34743 94 34 4 7086 24 4 4 33063 96 35 6 6813 26 3 3 31475 98 36 7 6551 28 2 2 29975 100 37 8 6301 30 1 1 28558 102 38 9 6062 32 0 0 27219 104 40 0 5834 34 1 1 25949 106 41 1 5614 36 2 2 24749 108 42 2 5404 38 3 3 23613 110 43 3 5203 40 4 4 22537 112 44 4 5010 42 5 6 21516 114 45 6...

Page 116: ...ank space or arrow in the lower right hand corner of the screen until the display changes hold for about 4 seconds Fig 311 2 Press REMOVE then YES to disconnect from the old thermostats 3 To reconnect the thermostat go to Linking RedLINK Accessories beginning on page 14 At the Indoor Sensor RedLINK Internet Gateway Entry Exit Remote Vent Filter Boost Remote or TrueSTEAM Wireless Adapter 1 Press an...

Page 117: ...age 2 Emergency Heat Stage 2 Y Compressor Stage 1 Y Compressor Stage 1 Y2 Compressor Stage 2 Y2 Compressor Stage 2 G Fan Relay G Fan Relay A Connect to Economizer Module or Lighting Panel TOD L A Connect to Compressor Monitor Zone Panel Economizer Module or Lighting Panel TOD U1 U1 U2 U2 U3 U3 Universal relay for humidification dehumidification ventilation or a stage of heating cooling U terminals...

Page 118: ...h excess wire back into the hole 5 Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat 6 See Fig 314 337 for typical wiring hookups Table 10 Thermostat Terminal Designation Descriptions Conventional System Heat Pump Terminal Description Terminal Description C Common wire from secondary side of cooling transformer if 2 transformers C Common wire from secondary...

Page 119: ...adiant heat with backup forced air heat Zoned with forced air zone panel and hot water panel 325 Hot water fan coil with forced air furnace backup heat 326 Wood stove with heat pump and backup electric strips For applications in which the thermostat only needs to run the blower fan when stove is hot Wiring IAQ Equipment or a stage of Heating Cooling to U1 U2 or U3 terminals 327 337 Wired Remote Se...

Page 120: ...sor return sensor dry contact device to display an alert or an occupancy sensor for remote setback 3Remove jumper s if using separate transformers 4See Economizer Module Wiring Diagrams beginning on page 132 5Connect wireless adapter to ABCD for extended wireless range HEAT STAGE 1 HEAT STAGE 2 HEAT STAGE 3 FAN TO THERMOSTAT STATUS LEDS JUMPERS SENSORS CONV FURNACE R C W W2 W3 G Y2 Y TRANSFORMER 1...

Page 121: ...setback 3L A terminal sends continuous output when thermostat is set to EM HEAT mode except when set up for Economizer or TOD See Economizer Module Wiring Diagrams beginning on page 132 4Connect wireless adapter to ABCD for extended wireless range CHANGEOVER VALVE BACKUP HEAT STAGE 1 FAN RELAY SENSORS TO THERMOSTAT HEAT PUMP AIR HANDLER TRANSFORMER 120 VAC 24 VAC COMPRESSOR STAGE 1 COMPRESSOR STAG...

Page 122: ...mizer Module Wiring Diagrams beginning on page 132 4Wire a maximum of 4 sensors using the S1 S4 terminals S1 S4 terminals can be connected to an indoor sensor outdoor sensor discharge sensor return sensor dry contact device to display an alert or an occupancy sensor for remote setback 5Connect wireless adapter to ABCD for extended wireless range NOTE For setup and operation see Geothermal Radiant ...

Page 123: ...R C ZONE VALVE TR TH END SWITCH 1 1 2 2 TRANSFORMER R IS JUMPERED TO RH 1 THERMOSTAT EIM W W2 W3 Y Y2 G A M34524 24 VAC 120 VAC R C SERIES 20 VALVE C R 5 B 4 W 6 1 TRANSFORMER REMOVE THE JUMPER FROM RH TO RC WHEN USED WITH AQ2000 SERIES PANEL 1 THERMOSTAT EIM RC RH W W2 W3 Y2 G M31479 24 VAC 120 VAC R C HOT WATER RELAY PANEL ZONE 1 RH W 1 O B AUX1 AUX2 O Y Y2 G R C L A TO THERMOSTAT THERMOSTAT EIM...

Page 124: ...jumper if radiant heat is powered by system transformer Do NOT install a field jumper if radiant heat has its own transformer 3L A terminal sends continuous output when thermostat is set to EM HEAT mode except when set up for Economizer or TOD See Economizer Module Wiring Diagrams beginning on page 132 4Y2 used with heat pumps that have 2 compressor stages NOTE For setup and operation see Geotherm...

Page 125: ...OR HEAT THE THERMOSTAT WILL ENERGIZE ONLY THE FAN WITH A CALL FOR STAGE 1 HEAT IF THE WOOD STOVE IS HOT HEAT COMES FROM THE FAN COIL IF THE WOOD STOVE IS COLD ONLY THE FAN RUNS THE THERMOSTAT WILL UPSTAGE TO THE FURNACE AS NEEDED TO MAINTAIN THE TEMPERATURE L TO THERMOSTAT THERMOSTAT EIM CONV FURNACE M31482 1 2 1 2 W W2 W3 W Y G R C THE BOILER IS CONTROLLING THE CIRCULATOR PUMP IN THIS DIAGRAM L T...

Page 126: ...el and zone valves TRANSFORMER 24 VAC 120 VAC M34526 ZONE VALVE TR TH END SWITCH C R W W2 W3 W Y G R C HZ311 HZ322 OR HZ432 ZONE PANELS COULD BE USED TO CONTROL A FORCED AIR FURNACE ZONED WITH DAMPERS THE BOILER IS CONTROLLING THE CIRCULATOR PUMP IN THIS DIAGRAM L TO THERMOSTAT THERMOSTAT EIM CONV ZONE 1 1 2 1 2 BOILER T T RELAY 3 1 ...

Page 127: ...322 OR HZ432 ZONE PANELS COULD BE USED TO CONTROL A FORCED AIR FURNACE ZONED WITH DAMPERS AN AQ2000 SERIES HOT WATER ZONE PANEL OR OTHER RELAY BASED HOT WATER ZONE 3 PANEL COULD BE USED L TO THERMOSTAT THERMOSTAT EIM CONV ZONE 1 ZONE 1 1 2 1 2 RELAY 3 1 W W2 W3 W Y G R C CONFIGURE THE THERMOSTAT TO ENERGIZE THE FAN WITH A CALL FOR HEAT THE BOILER IS CONTROLLING THE CIRCULATOR PUMP IN THIS DIAGRAM ...

Page 128: ...us output when thermostat is set to EM HEAT mode except when set up for Economizer or TOD See Economizer Module Wiring Diagrams beginning on page 132 4Y2 used with heat pumps that have 2 compressor stages NOTE In Fig the thermostat will energize only the fan with a call for stage 1 heat If the wood stove is hot heat comes from the fan coil If the wood stove is cold only the fan runs The thermostat...

Page 129: ...ally open dry contacts when set up for a stage of heating or cooling 2You must install a field jumper if the stage of heating or cool ing is powered by system transformer Do NOT install a field jumper if the stage of heating has its own transformer Normally open dry contacts Normally closed dry contacts C K RC R U1 U1 120 VAC 24 VAC C R SYSTEM TRANSFORMER 120 VAC 24 VAC HUM DEHUM OR VENT TRANSFORM...

Page 130: ... universal EIM relay to the low speed fan for dehumidification control at the equipment The EIM relay can be set to be normally open or normally closed in the thermostat installer setup POWERED HUMIDIFIER RH RC R C U3 U3 U2 U2 U1 U1 MCR32393A 24 VAC 120 VAC 24 VAC 120 VAC 24 VAC 1 POWERED VENTILATOR RH RC R C 24 VAC U3 U3 U2 U2 U1 U1 MCR32396A 24 VAC 120 VAC 24 VAC 120 VAC 1 POWERED DEHUMIDIFIER R...

Page 131: ...cts when set up for a stage of heating or cooling 2You must install a field jumper if the stage of heating or cooling is powered by the system transformer Do NOT install a field jumper if the stage of heating has its own transformer 1 2 U3 U3 U2 U2 U1 U1 120 VAC 24 VAC 24 VAC HEAT STAGE 3 COOL STAGE 3 COOL STAGE 4 OR GEOTHERMAL RADIANT HEAT RH RC R C TRANSFORMER ...

Page 132: ...X 2 is present only on the Equipment Interface Module 3Connect the changeover valve from the roof top unit to the normally open contacts of an isolation relay to prevent feedback into the economizer module during defrost If this is not done when the system goes into defrost it will change the economizer into cooling mode due to the feedback and open the outside damper while in heating mode 120 VAC...

Page 133: ...er setup ISU 222 These terminals are powered by the cool ing transformer Rc terminal 2Terminal AUX 2 is present only on the Equipment Interface Module 3Add a normally closed relay as shown to make the W7213 W7214 Economizer Module compatible with the thermostat The ther mostat energizes the A or L A terminal during Occupied Periods 120 VAC Y1 Y2 AUX AUX 2 G 24 VAC O OR B N 3 4 1 2 5 TR1 TR Rooftop...

Page 134: ...ntrol contactors or near light dimming circuits electric motors or welding equipment Avoid poor wiring connections Avoid intermittent or missing building earth ground CAUTION Electrical Shock Hazard Can cause electrical shock or equipment damage Disconnect power supply before connecting wiring Wiring must comply with applicable codes ordinances and regulations 1 Wire C7089U1006 Outdoor Sensor to S...

Page 135: ...al Shock Hazard Can cause electrical shock or equipment damage Disconnect power supply before connecting wiring Use the S1 S2 S3 or S4 terminals for wired sensors Wiring 4 C7189U1005 sensors 10k ohm for temperature averaging network Select 10K in the Installer Setup ISU 503 when using C7189U1005 sensor s Fig 343 Wiring 4 C7189U sensors Wiring 2 TR21 sensors 20k ohm and 1 TR21 A sensor 10k ohm for ...

Page 136: ...2 2 2 R C CONNECT POWER THM4000R CONNECTED WIRELESS SETUP 1 3 3 1 VISIONPRO THERMOSTATS CAN BE POWERED BY ANY TRANSFORMER IN THIS EXAMPLE THEY ARE POWERED BY THE SAME TRANSFORMER THAT POWERS THE HZ432 THERE CAN BE UP TO 4 VISIONPRO THERMOSTATS USED WITH A SINGLE THM4000R WIRELESS ADAPTER AND HZ432 ZONE PANEL THE THM4000R CANNOT BE USED IF THERE ARE MORE THAN 4 ZONES IN THE SYSTEM RH RC JUMPER INST...

Page 137: ...E 4 DAMPER THERMOSTAT EQUIPMENT POWER SENSORS ACCESSORIES R C C7735A1000 DATS A B C D WIRELESS C R W W2 Y Y2 G FURNACE AFS 5 4 1 5 2 2 R C 1 4 3 3 1 A DEDICATED TRANSFORMER SHOULD POWER THE HZ432 IF A DIFFERENT TRANSFORMER IS USED TO POWER THE EIM THE JUMPER FROM R TO RH NEEDS TO BE REMOVED AND THE RH AND RC FROM EIM GETS WIRED TO R ON THE ZONE THAT THE EIM IS WIRED TO THE VISIONPRO THERMOSTAT CAN...

Page 138: ... To dehumidify in all zones set ISU 913 Dehum Fan Control to Equip Controls Fan RH RC W1 E W2 W3 Y1 Y2 G O B DS BK M34529 EQUIPMENT C R W Y G FURNACE TrueZONE PANEL VisionPRO EIM ERV HRV INTERLOCK B G R AUX W B G R 2 2 1 1 SELECT THE TERMINALS WIRED TO THE VENTILATOR AT ISU 1002 U1 U2 U3 TO VENTILATE IN ALL ZONES SET ISU 1006 VENT FAN CONTROL TO EQUIP CONTROLS FAN FOR ALL ZONE PANEL WIRING NOT SHO...

Page 139: ... one of the zones A single THM4000R1000 wireless adapter allows you to connect up to three RedLINK VisionPRO thermostats with an HZ322 or up to four RedLINK VisionPRO thermostats with an HZ432 HZ432 with a TAZ 4 add a zone You cannot use a wireless adapter when a TAZ 4 is used Each RedLINK VisionPRO thermostat used would need a separate THM5421R Equipment Interface Module or you can wire the RedLI...

Page 140: ...or these transmitters must be installed to provide a separation distance of at least 20 cm from all persons and must not be co located or operating in conjunction with any other antenna or transmitter Portable Comfort Control This portable transmitter with its antenna complies with FCC and Industry Canada RF exposure limits for general population uncontrolled exposure This device must not be co lo...