VISIONPRO
®
8000 WITH REDLINK™
45
68-0312—03
604
Remote Setback
Heat Setpoint
50° F to 70° F
64° F
Commercial Yes
Remote Setback requires an EIM (Equipment
Interface Module).
During occupied periods, the occupancy
sensor tells the thermostat to go to setback
settings when no one is in the room. If
someone is in the room, then it follows the
settings of the occupied period. The
occupancy sensor is ignored during
unoccupied periods.
If the thermostat is setup for non-
programmable, the occupancy sensor tells the
thermostat to go to setback settings when no
one is in the room. If someone is in the room,
then it follows the settings set by the user.
605
Drain Pan Alert
None
S1
S2
S3
S4
None
Both
Yes
Dry Contact Alerts require an Equipment
Interface Module.
Select the terminals wired to the Full Drain
Pan Dry Contact Device.
606
Drain Pan Alert is
[See Settings]
Normally Open
Normally Closed
Normally Open Both
Yes
Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed.
Normally Open: The Dry Contact device is
normally open and will close when the device
detects the drain pan is full.
Normally Closed: The Dry Contact device is
normally closed and will open when the device
detects the drain pan is full.
607
Dirty Filter Alert
None
S1
S2
S3
S4
None
Both
Yes
Dry Contact Alerts require an Equipment
Interface Module.
Select the terminals wired to the Dirty Filter
Dry Contact Device.
608
Dirty Filtr Alert is
[See Settings]
Normally Open
Normally Closed
Normally Open Both
Yes
Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed:
Normally Open: The Dry Contact device is
normally open and will close when the device
detects a dirty filter.
Normally Closed: The Dry Contact device is
normally closed and will open when the device
detects a dirty filter.
609
Water Leak Alert
None
S1
S2
S3
S4
None
Both
Yes
Dry Contact Alerts require an Equipment
Interface Module.
Select the terminals wired to the Water Leak
Dry Contact Device (wet switch).
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Requires
EIM
Notes