10
Technical Data
Honeywell
3
Ambient
conditions
Ambient operating
temperature
14°F(-10°C) (no frost)…+104/122°F(+40/
50°C)(depends on the unit size): rated loada-
bility I
N
Storage temperature
-40°F(-40°C)....+158°F(+70°C)
Relative humidity
0…95% RH, non-condensing, non-corro-
sive, no dripping water
Air quality:
chemical vapours
mech. particles
IEC 721-3-3, unit in operation, class 3C2
IEC 721-3-3, unit in operation, class 3S2
Altitude
100% load capacity (no derating) up to
1000m(3281ft). 1% derating for each
100m(328.1ft) above 1000m (3281ft); max.
2000m (6562ft)
Vibration:
EN60068-2-6
3...150 Hz
Displacement amplitude 1(peak) mm at
3...15.8 Hz Max acceleration amplitude 1 G
at 15.8...150 Hz
Shock
IEC 68-2-27
UPS Drop Test (for applicable UPS weights)
Storage and shipping: max 15 G, 11 ms (in
package)
Enclosure class
IP20
(Open Chassis), option: NEMA 1
Pollution degree
PD2
EMC
Immunity
Complies with EN50082-1, -2, EN61800-3
Emissions
115V: Complies with EMC category C4
230V : Complies with EMC category C2; With
an internal RFI filter
400V: Complies with EMC category C2; With
an internal RFI filter
600V: Complies with EMC category C4
All: No EMC emission protection (Honeywell
level N): Without RFI filter
Standards
For EMC: EN61800-3,
For safety: UL508C, EN61800-5-1
Certificates and
manufacturer’s
declarations of
conformity
For safety: CB, CE, UL, cUL,
For EMC: CE, CB, c-tick
(see unit nameplate for more detailed
approvals)
Table 3.1 : SmartVFD COMPACT technical data