5. COMMISSIONING
Before commissioning, note the warnings and instructions listed in
Chapter 1!
5.1 COMMISSIONING STEPS OF SMARTVFD COMPACT
1
Read carefully the safety instructions in Chapter 1 and follow them.
2
After the installation, make sure that:
• both the frequency converter and the motor are grounded.
• the mains and motor cables comply with the requirements given
in Chapter 4.2.3.
• the control cables are located as far as possible from the power
cables (see Chapter 4.2.4, step 2) and the shields of the
shielded cables are connected to protective ground.
3
Check the quality and quantity of cooling air (Chapter 4.1.2).
4
Check that all Start/Stop switches connected to the I/O terminals are in
Stop
-position.
5
Connect the frequency converter to mains.
Note: The following steps are valid if you have API Full or API Limited
Application Interface in your SmartVFD COMPACT.
6
Set the parameters of group 1 according to the requirements of your
application. At least the following parameters should be set:
• motor nominal voltage (par. 1.1)
• motor nominal frequency (par. 1.2)
• motor nominal speed (par. 1.3)
• motor nominal current (par. 1.4)
You will find the values needed for the parameters on the motor rating
plate.