92(96)
Honeywell
Honeywell
Honeywell
Honeywell
10
10. DESCRIPTION OF EXPANDER BOARD NXLOPTAA
Description: I/O expander board with one relay output, one open collector output
and three digital inputs.
Allowed slots:
Honeywell NXL
board slot E
Type ID:
16705
Terminals:
Two terminal blocks; Screw terminals (M2.6 and M3); No coding
Jumpers:
None
Board parameters:
None
I/O terminals on NXLOPTAA
Terminal
Parameter
setting
Description
X3
1
+24V
Control voltage output; voltage for switches etc, max. 150 mA
2
GND
Ground for controls, e.g. for +24 V and DO
3
DIN1
DIGIN:x.1
Digital input 1
4
DIN2
DIGIN:x.2
Digital input 2
5
DIN3
DIGIN:x.3
Digital input 3
6
DO1
DIOUT:x.1
Open collector output, 50mA/48V
X5
24 RO1/NC
DIOUT:x.2
25 RO1/C
26 RO1/NO
Relay output 1 (NO)
Switching capacity:
24VDC/8A
250VAC/8A
125VDC/0,4A
Table 10-1. I/O terminals of board NXLOPTAA
Note!
The +24 V control voltage terminal can also be used to power the control module (but not the
power module).