Power ratings
4.2.1 NXL Compact – Mains voltage 208 – 240 V & 380 – 500 V
Mains voltage 208-240 V, 50/60 Hz, 1~/3~ Series NXL Compact
Loadability
Motor shaft
power
Low
High
Frequency
converter type
Rated
con-
tinuous
current
I
L
(A)
10%
over-
load
current
(A)
Rated
continuous
current I
H
(A)
50%
overload
current
(A)
Low
40°C
P(kW)
High
50°C
P(kW)
Nominal
input
current
1~/3~
Mechanical
size
Enclosure
and
protection
class
Dimensions
WxHxD
Weight
(kg)
NXL 0002 2
2,4
2,6
1,7
2,6
0,37
0,25
4,8/--
MF2/IP20
60x130x150
1,0
NXL 0003 2
3,7
4,1
2,8
4,2
0,75
0,55
7,4/5,6
MF3/IP20
84x184x172
1,9
NXL 0004 2
4,8
5,3
3,7
5,6
1,1
0,75
9,6/7,2
MF3/IP20
84x184x172
1,9
E
M
C
-l
e
v
e
l
N
NXL 0006 2
6,6
7,3
4,8
7,2
1,5
1,1
13,2/9,9
MF3/IP20
84x220x172
2,0
Table 4-1. Power ratings and dimensions of NXL, supply voltage 208-240V.
NOTE!
NXL 0002 2 is suitable for single phase supply only
Mains voltage 380-500 V, 50/60 Hz, 3~ Series NXL Compact
Loadability
Motor shaft power
Low
High
400V supply
500V supply
Frequency
converter type
Rated
con-
tinuous
current
I
L
(A)
10%
over-
load
current
(A)
Rated
con-
tinuous
current
I
H
(A)
50%
over-
load
current
(A)
10%
over-
load
40°C
P(kW)
50%
over-
load
50°C
P(kW)
10%
over-
load
40°C
P(kW)
50%
over-
load
50°C
P(kW)
Nominal
input
current
Mechanical
size
Enclosure
and
protection
class
Dimensions
WxHxD
Weight
(kg)
NXL 0001 5
1,9
2,1
1,3
2
0,55
0,37
0,75
0,55
2,9
MF2/IP20
60x130x150
1,0
NXL 0002 5
2,4
2,6
1,9
2,9
0,75
0,55
1,1
0,75
3,6
MF2/IP20
60x130x150
1,0
NXL 0003 5
3,3
3,6
2,4
3,6
1,1
0,75
1,5
1,1
5,0
MF3/IP20
84x220x172
2,0
NXL 0004 5
4,3
4,7
3,3
5
1,5
1,1
2,2
1,5
6,5
MF3/IP20
84x220x172
2,0
E
M
C
-l
e
v
e
l
N
NXL 0005 5
5,4
5,9
4,3
6,5
2,2
1,5
3
2,2
8,1
MF3/IP20
84x220x172
2,0
Table 4-2. Power ratings and dimensions of NXL, supply voltage 380-500V.