Cabling and connections
45(96)
6
6.2.4 Control I/O
Terminal
Signal
Description
1
+10V
ref
Reference output
Voltage for potentiometer, etc.
2
AI1+
Analogue input, voltage range
0—10V DC.
Voltage input frequency reference
3
AI1-
I/O Ground
Ground for reference and controls
4
AI2+
5
AI2-
/GND
Analogue input, current range
0—20mA
Current input frequency reference
6
+24V
Control voltage output
Voltage for switches, etc. max 0.1 A
7 GND
I/O ground
Ground for reference and controls
8
DIN1
Start forward (programmable)
Contact closed = start forward
9
DIN2
Start reverse (programmable)
Contact closed = start reverse
10
DIN3
Preset speed selection 1
(programmable)
Contact closed = Preset speed 1
11
GND
I/O ground
Ground for reference and controls
18
AO1+
19
AO1-
Output frequency
Analogue output
Programmable
Range 0—20 mA/R
L
, max. 500
Ω
A
RS 485
Serial bus
Differential receiver/transmitter
B
RS 485
Serial bus
Differential receiver/transmitter
30
+24V
24V aux. input voltage
Control power supply backup
21
RO1
22
RO1
23
RO1
Relay output 1
FAULT
Programmable
Table 6-7. Default I/O configuration.
Terminal
Signal
Description
12
+24V
+24 V DC
Control voltage output; voltage for
switches etc.
13
GND
I/O ground
Ground for reference and controls
14 Exp DIN1 Preset speed selection 2
(programmable)
Contact closed = Preset speed 2
15 Exp DIN2 Fault Reset
(programmable)
Contact closed = Fault reset
16 Exp DIN3 Disable PID (PID control
selection)
(Programmable)
Contact closed = Disable PID
25 Exp RO1
26 Exp RO1
Expander Relay output 1 (NO)
RUN
Programmable
28
TI+
29
TI-
Motor Thermistor input
Active = Fault, stop according to defined
method
Table 6-8. Additional inputs in
NXL HVAC
(available as option for NXL Compact)
Terminal
Signal
Description
1
+10V
ref
Reference output
Voltage for potentiometer, etc.
2
AI1+
or
DIN 4
Analogue input, voltage range
0—10V DC
Voltage input frequency reference (MF2-3)
Voltage/current input frequency reference
(MF4-MF6)
Can be programmed as DIN4
3
AI1-
I/O Ground
Ground for reference and controls
4
AI2+
5
AI2-
/GND
Analogue input, voltage range
0—10V DC or current range
0—20mA
Voltage or current input frequency
reference
6
+ 24 V
Control voltage output
7 GND
I/O ground
Ground for reference and controls
Table 6-9. AI1 configuration, when programmed as DIN4
Reference
Potentiometer 1-10
k
Ω
mA