88(96)
Commissioning
Honeywell
Honeywell
Honeywell
Honeywell
8
P2.1.16
P2.1.15.16
Analogue
output
function
0
12
1
307
0
=Not used
1
=Output freq. (0—f
max
)
2
=Freq. reference (0—f
max
)
3
=Motor speed (0—Motor
nominal speed)
4
=Output current (0—
I
nMotor
)
5
=Motor torque (0—T
nMotor
)
6
=Motor power (0—P
nMotor
)
7
=Motor voltage (0—
U
nMotor
)
8
=DC-link volt (0—1000V)
9
=PI controller ref. value
10
=PI contr. act. value 1
11
=PI contr. error value
12
=PI controller output
P2.1.17
P2.1.15.17
DIN2
function
0
10
1
319
0
=Not used
1
=Start Reverse
2
=Reverse
3
=Stop pulse
4
=External fault, cc
5
=External fault, oc
6
=Run enable
7
=Preset speed 2
8
= Motor pot. UP (cc)
9
= Disable PID (Direct freq.
reference)
10
=Interlock 1
P2.1.18
P2.1.15.18
DIN3
function
0
17
6
301
0
=Not used
1
=Reverse
2
=External fault, cc
3
=External fault, oc
4
=Fault reset
5
=Run enable
6
=Preset speed 1
7
=Preset speed 2
8
=DC-braking command
9
=Motor pot. UP (cc)
10
=Motor pot. DOWN (cc)
11
=Disable PID (PID
control selection)
12
=PID Keypad ref. 2
selection
13
=Interlock 2
14
=Thermistor input (
See
Chapter 6.2.4
)
15
=Force CP to I/O
16
=Force CP to Fieldbus
17
=AI1/AI2 selection
P2.1.19
P2.1.15.19
Preset
speed 1
0,00
Par. 2.1.2
Hz
10,00
105
P2.1.20
P2.1.15.20
Preset
speed 2
0,00
Par. 2.1.2
Hz
50,00
106
P2.1.21
P2.1.15.21
Automatic
restart
0
1
0
731
0
=Not used
1
=Used
P2.1.22
Parameter
conceal
0
1
0
115
0
=All parameters and
menus visible
1
=Only group P2.1 and
menus M1 – H5 visible
Table 8-3. Basic parameters P2.1
*
Start mode where Trip Free Output Switching is enabled, recommended to be used with all pump and fan
applications.
**
Default values if Start-up wizard has not been used. Look Figure 7-3 on page 54 or
NXL HVAC Quick
Guide
to see the values with different modes in wizard.
9.
FAULT TRACING
When a fault is detected by the frequency converter control electronics, the drive is stopped and the
symbol
F
together with the ordinal number of the fault and the fault code appear on the display. The