7
7.4.8.2
Termination Resistor
The RS-485 bus is terminated with 120
Ω
termination resistors in both ends. NXL has a built-in
termination resistor which is switched off as a default. See the jumper selections in chapter 6.2.5.1
7.4.8.3
Modbus address area
The Modbus bus of NXL uses the ID numbers of the application as addresses. The ID numbers can
be found in the parameter tables of the Application manual.
When several parameters/monitoring values are read at a time they must be consecutive. 11
addresses can be read and the addresses can be parameters or monitoring values.
7.4.8.4
Modbus process data
Process data is an address area for fieldbus control. Fieldbus control is active when the value of
parameter 3.1 (Control place) is
2
(=fieldbus). The contents of the process data has been
determined in the application. The following tables present the process data contents in the Multi-
Control Application.
Output Process data
Addr.
Modbus register
Name
Scale
Type
2101
32101, 42101
FB Status Word
-
Binary coded
2102
32102, 42102
FB General Status Word
-
Binary coded
2103
32103, 42103
FB Actual Speed
0,01
%
2104
32104, 42104
Motor speed
0,01
+/- Hz
2105
32105, 42105
Motor speed
1
+/- Rpm
2106
32106, 42106
Motor current
0,1
A
2107
32107, 42107
Motor Torque
0,1
+/- % (of nominal)
2108
32108, 42108
Motor Power
0,1
+/- % (of nominal)
2109
32109, 42109
Motor Voltage
0,1
V
2110
32110, 42110
DC Voltage
1
V
2111
32111, 42111
Active Fault
-
Fault code
Input Process data
Addr.
Modbus register
Name
Scale
Type
2001
32001, 42001
FB Control Word
-
Binary coded
2002
32002, 42002
FB General Control Word
-
Binary coded
2003
32003, 42003
FB Speed Reference
0,01
%
2004
32004, 42004
PID Control Reference
0,01
%
2005
32005, 42005
PID Actual Value
0,01
%
2006
32006, 42006
-
-
-
2007
32007, 42007
-
-
-
2008
32008, 42008
-
-
-
2009
32009, 42009
-
-
-
2010
32010, 42010
-
-
-
2011
32011, 42011
-
-
-