Fire Alarm Control Panel IQ8Control C / M
94
FB 798951.10.GB0 / 04.15
RS232 / TTY module (Part No. 784842)
Serial interface, alternatively RS232- or TTY
(20 mA) to connect external devices e.g. management
systems, Printers, Remote indicator panels etc.
Quiescent current
: approx. 35 mA @i RS232
approx. 55 mA @i TTY
RxD (receive)
Data GND (potential free)
TxD (transmitt)
not used
1
2
3
4 5
6
7
8
not used
not used
not used
not used
1
2
3
4 5
6
7
8
Tx - (transmitt)
Rx + (receive)
Tx + (transmitt)
Rx - (receive)
not used
not used
not used
not used
3 Relay module (Part No. 787531)
Three bistable relay (monitoring possible) with
programmable operation mode normally open or normally
close.
Contact rating: max. 30 V DC / 1 A
Quiescent current
: approx. 5 mA
1
2
3
4 5
6
7
8
ext. device to relay K 1
ext. device to relay
K 2
ext. voltage e. g. +12 V
-
+
+
+
+
-
-
-
ext. device to relay
K 2
1
2
3
4 5
6
7
8
ext. device to relay
K 1
ext. device to relay K 2
+
+
+
+
-
-
-
-
ext. voltage for ext. device
to Relay K 1 e. g. +12 V
ext. voltage for ext. device
to Relay K 2 e. g. +24 V
3 Relay common fault module (Part No. 787532)
Three bistable relay (monitoring possible) with
programmable operation mode normally open or normally
close and an additional common fault relay (energized in
normal mode).
Contact rating: max. 30 V DC / 1 A
Quiescent current
: approx. 15 mA
Observe permitted torque (max. 0.4 Nm) of the terminals!