10.8 Display of the event memory
At the installer level, the event memory of the Fire Alarm Control Panel can be shown on the display by pressing
the >Event mem< key. The last 200 events, such as alarms, malfunctions, switch-offs and operating authorisations
are stored in the event memory in chronological order. The display shows the latest event.
The events are automatically numbered with consecutive report numbers. The higher the report number, the
more recent is the event (report number 001 = oldest event).
End
Signal 078
10:12 17.10
wire brk.
Event memory
Zone : 004 Detector : 01
3rd floor, conference room
TROUBLE
Fig. 97: Event memory
It is possible to browse the event memory for individual events using the cursor keys.
Fig. 98: Cursor keys
10 events forward
To next younger event
10 events backwards
To next older event
Printing the contents of the event memory
Pressing the >Printing< function key moves automatically to the >Printer functions< menu.
This allocation can be removed by pressing the >Zone< key and the desired printer number, e.g. for an external
protocol printers, can be entered. All entries (max. 200) of the event memory are printed out ordered from the
most recent to the oldest event. (see “Printing out the event memory“).